113
APPENDIX D: SystemVut Controller CCN Tables
Service Config Tables (cont)
TABLE DISPLAY NAME VALUES UNITS POINT NAME WRITE STA TUS
HEATCFG
Type of Heat Installed 0to1 HEATTYPE 0: 50 Series
1: 48 Series
0=Electric
1=Gas
Number Of Heating Stages 0to2 NUMHSTGS 2: all except below
0: 50 Series without FIOP heaters
1: 48 Series single phase power,
Low Nox Gas Heat,
48FC 04--- 07 Low Heat,
48FC 05--- 07 Med Heat,
50GC 04--- 06 Low Heat ,
50GC 04--- 05 Med Heat,
50GC 04 High Heat 230v 3ph and 460v,
50GC 05 High Heat 230v 3ph,
50GC 06 Med Heat 460v and 575v
Heat Minimum On Time 60 to 600 sec H_MINON 120
Heat Minimum Off Time 60 t o 600 sec H_MINOFF 120
Heat Stage Increase Time 120 to 999 sec HSTAGINC 450
Heating SAT Trend Level --- 1 t o 1 SAT_TLH 0.2
Heat Max SAT Lower Level 85 to 200 °F SATMAX_L 140
Heat Max SAT Upper Level 85 to 200 °F SA TMAX_H 170
Heating Fan--- Off Delay 10 to 600 sec HEAT_FOD 30: 50 Series
45: 48 Series
Heating Lockout Temp 40 to 125 °F OATLHEAT 75
SAT heat mode sensing Enable/Disable SAT_HEAT Enable
No IGC IFO input Timeout 0to60 min NO_IGCTM 5
Pre--- Heat HX without IDF? Enable/Disable PREHT_HX Disable
Supply Air Temper Enable Yes/No SATEMPEN No
SA t empering Set point 35 to 80 °F SATEMPSP 55
Max OAT for SA tempering 40 to 80 °F OATSTEMP 65
ECON_CFG
Ventilation Method 0to4 VENTTYPE 0: No FIOP
1: Economizer FIOP
2: Two Position Damper FIOP
0=None
1 = Economizer
2 = 2 --- P o s i t i o n D a m p e r
3=ERV
4 = Economizing ERV
Econ Max Damper Position 0 to 100 % DAMPMAX 100
Economizer Travel Time 5 to 300 sec ECONOTRV 150
IDF Maximum Fan Speed 0 t o 100 % SPEEDMAX 100
Econ Min at Max Fanspeed 0 t o 100 % MINP_MAX 30
Min Pos --- User Speed 1 0 to 100 % MP_USPD1 0
M i n P o s --- U s e r P o s 1 0 to 100 % MP_UPOS1 0
Min Pos --- User Speed 2 0 to 100 % MP_USPD2 0
M i n P o s --- U s e r P o s 2 0 to 100 % MP_UPOS2 0
Min Pos --- User Speed 3 0 to 100 % MP_USPD3 0
M i n P o s --- U s e r P o s 3 0 to 100 % MP_UPOS3 0
LowFree Cool SAT Setpnt 40 to 80 °F LCSASP 65
High FreeCool SAT Setpnt 40 to 80 °F HCSASP 55
Free Cooling Max OAT 0to90 °F MAXFREET 65
Free Co oling Min Temp --- 30 t o 70 °F MINFREET 0
Diff. Dry Bulb Control Enable/Disable DIFFBULB Disable
Diff. Dry Bulb Deadband 0to20 °F OATRATDB 3
Max Enthalpy OA limit 1to99 BTU_LB FREEMAXE 28
Diff. Enthalpy Control Enable/Disable DIFFENTH Disable
Enthalpy Cross Deadband 0to20 BTU_LB OAERAEDB 2
E C O N O P I D --- K P 0.00 to 99.90 ECONO_P 2.5
E C O N O P I D --- K I 0.00 to 99.90 ECONO_I 0.12
E C O N O P I D --- K D 0.00 to 99.90 ECONO_D 1
E C O N O P I D --- R A T E 10 to 180 sec ECONO_DT 15