86
APPENDIX C: Navigatort Display
MODE -- SERVICE TEST
ITEM EXPANSION VALUES UNIT WRITE STA TUS POINT
SERVICE TEST Service Test Menu
TEST ServiceTestModeEnable On/Off
INDP INDEPENDENT TEST MENU
DAMP Economizer Position Test 0 t o 100 % S_DAMPER
BMP1 Compressor Bump A1 Test On/Off S_BMP A1
RDV.A Rht Dischg Valve Rly Tst On/Off S_RDV_A
RL.VA Reheat Liq Valv Rly Test On/Off S_RLV_A
CL.VA Cooling Liq Valv Test On/Off S_CLV_A
CCH1 Crankcase Heater 1 test On/Off S_CCHR1
ALRM Alarm Output Relay Test On/Off S_ALARM
PE1 Power Exhaust 1 Test On/Off S_PE_1
PE2 Power Exhaust 2 Test On/Off S_PE_2
2P.EV 2Position/ERV Relay Test On/Off S_ERV2P
FAN FAN TESTS
IDFS Indoor Fan Speed Test 0 to 100 % S_IDFSPD
IF.SP Converted IDF Speed 0 to 5000 RPM IFRPMTST
IF.TR IDF Manual T ransition Yes/No S_IDFTRN
COOL Cooling Test Menu
CL.A1 Cooling W/Comp.A1 Test On/Off S_COOLA1
CL.AL Cooling W/Comp.ALD Test On/Off S_COLALD
IDFS Indoor Fan Speed Test 0 to 100 % S_IDFSPD
OFR ODF Speed Relay Test On/Off S_OFRSPD
HUM.T Humidimizer Level Test 0=Off,
1=Subcool,
2=Reheat
S_HMZLEV
HEAT H eating Test Menu
HT.1 Heating Stage 1 Test On/Off S_HEAT1
HT.2 Heating Stage 2 Test On/Off S_HEAT2
IDFS Indoor Fan Speed Test 0 to 100 % S_IDFSPD