APPENDIX C: Navigatort Display
MODE -- TEMPERATURES
ITEM EXPA NSION VALUES UNITS
WRITE
STATUS
POINT
TEMPERATURES Temperature Menu
SAT Supply Air Temperature xxx..x °F SA T
OAT Outdoor Air Temperature xxx.x °F Forcible OAT
RAT Return Air Temperature xxx.x °F Forcible RAT
SPT Space Temperature xxx.x °F Forcible SPACE_T
SPTO Space Temperature Offset xx.x ΔF Forcible SPTO
SST.A Cir . A Sat.Suction Temp xxx.x °F SST_A
SDT.A Cir.A Sat.Discharge Temp xxx.x °F SDT_A
FST Fan Supply Air Temp xxx.x °F FST
MODE -- PRESSURES
ITEM EXPA NSION VALUES UNITS
WRITE
STATUS
POINT
PRESSURES Pressures Menu
SSP.A Cir . A Suction Pressure xxx.x PSI SSP_A
SDP.A Cir. A Discharge Pressure xxx.x PSI SDP_A
PR.A Circuit A Pressure Ratio xx.xx CIRA_PR
BARP Barometric Pressure xx.xx Forcible BARP
MODE -- SETPOINTS
ITEM EXPA NSION VALUES UNITS DEFAULT POINT
SETPOINTS Setpoint Menu
OCSP Occupied Cool Setpoint 55 to 80 °F 78 OCSP
OHSP Occupied Heat Setpoint 55 to 80 °F 68 OHSP
UCSP Unoccupied Cool Setpoint 65 t o 95 °F 85 UCSP
UHSP Unoccupied Heat Setpoint 40 to 80 °F 60 UHSP
GAP H eat---Cool Setpoint Gap 2to10 °F 5 HC SP_GAP
STO.R SPT Offset Range (+/--- ) 0to5 °F 5 SPTO_RNG
RH.OS Occupied SPRH Setpoint 0 to 100 % 50 SPRH_OSP
RH.US Unoccupied SPRH Setpoint 0 to 100 % 80 SPRH_USP
RH.DB Space RH Deadband 2to20 % 8 SPRH_DB