APPENDIX C: Navigatort Display
MODE -- INPUTS
ITEM EXPANSION VALUES UNITS
WRITE
STATUS
POINT
INPUTS Inputs Menu
STAT Thermostat Inputs menu
G Thermostat G Input On/Off Forcible G
Y1 Thermostat Y1 Input On/Off Forcible Y1
Y2 Thermostat Y2 Input On/Off Forcible Y2
W1 Thermostat W1 Input On/Off Forcible W1
W2 Thermostat W2 Input On/Off Forcible W2
SW Switch Inputs Menu
IFO IGC Fan On Request (IFO) On/Off IGC_IFO
HPS.A Cir.A High Pressure Sw Open/Close CIRA_HPS
HUMD Humidistat Input On/Off Forcible HUMDSTAT
F. L S M IDF Manual Limit Switch Open/Close IDF_LSM
FDWN Fire Shutdown Switch Alarm/Normal Forcible FIREDOWN
COFS COFS Switch State High/Low Forcible COFS
PMR Phase Monitor Switch Alarm/Normal PMR_STAT
FIL.S Filter Status Switch Dirty/Clean Forcible FILTSTAT
RM.OC Remote Occupancy Switch On/Off Forcible REMOCC
R.OFF Remote Shutdown Switch On/Off Forcible REMSHUT
FAN.S Fan Status Switch On/Off FAN_STAT
GEN.S General Status Switch Alarm/Normal Forcible GENSTAT
IAQ.O IAQ Override Switch On/Off Forcible IAQ_OVRS
ENTH Enthalpy Switch High/Low Forcible ENTH_SW
AIS ANALOG Inputs Menu
EC.AP Damper Actual Position 0 to 100 % DAMPPOS
SPRH Space Relative Humidity 0 to 100 % Forcible SPRH
OARH OA Relative Humidity 0 to 100 % Forcible OARH
RARH RA Re lative H umidity 0 to 100 % Forcible RARH
IAQ Indoor Air Quality Level xxxx PPM Forcible IAQ
OAQ OA Quality Level xxxx PPM Forcible OAQ
OCFM Outdoor Air in CFM 0 to 8000 CFM Forcible OACFM
GEN General Inputs Menu
FT.RM Filter hour remaining xxxx hrs FILTLEFT
R.FLT Reset Filter Timer Ye s/No RESETFLT
OAE Outdoor Air Enthalpy --- 9.6 to 334.2 Forcible OA_ENTH
RAE Return Air Enthalpy --- 9.6 to 334.2 Forcible RA_ENTH
DF.AQ Differential Air Quality --- 5000 to 5000 PPM AQ_DIFF