7 - POSITIONING AND INSTALLATION
7.7 - Recommended service clearance
Important: This is the minimum space required for maintenance operations and access inside the unit. Depending on the assembly
selected for the unit and the characteristics of the installation site, a larger space around it may be required to ensure proper air
circulation and therefore the correct operation of the unit.
A
B
C
D
A
B
C
D
50FF/FC 052-058-062-070-074-086-093: R1 and R2 assemblies
50FF/FC 052-058-062-070-074-086-093: RW assembly
50FF/FC 052-058-062: RP assembly
50FF/FC 070-074-086-093: RP assembly
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
052 to 062 3.000 2.200 1.230 1.000 1.000 1.300 2.200
070 to 093 3.650 2.200 1.230 1.000 1.000 1.600 2.200
A
B
C
D
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
052 to 062 3.865 2.200 1.230 1.000 1.000 1.300 2.200
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
070 to 093 3.655 2.210 1.905 1.000 1.000 1.600 2.200
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
052 to 062 4.675 2.210 1.905 1.000 1.000 1.300 2.200
070 to 093 4.465 2.210 1.905 1.000 1.000 1.600 2.200
NOTE:
- Unit not designed to have overhead obstruction.
A
B
C
D