EasyManua.ls Logo

Carrier 50FF 020 - Recommended Service Clearance

Carrier 50FF 020
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
7 - POSITIONING AND INSTALLATION
7.7 - Recommended service clearance
Important: This is the minimum space required for maintenance operations and access inside the unit. Depending on the assembly
selected for the unit and the characteristics of the installation site, a larger space around it may be required to ensure proper air
circulation and therefore the correct operation of the unit.
50FF/FC 020-028-037-040-045-047: B1, B2 and BF assemblies
A
B
C
D
A
B
C
D
50FF/FC 020-028-037-040-045-047: BW assembly
50FF/FC 020-028-037-040-045-047: B3, BX, BP and BA assemblies
50FF/FC 020-028-037-040-045-047: BT and BB assemblies
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.225 1.750 1.230 1.200 1.000 1.000 1.600
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.230 1.755 1.905 1.200 1.000 1.000 1.600
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.230 1.760 1.975 1.200 1.000 1.000 1.600
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.230 2.565 1.905 1.200 1.000 1.000 1.600
A
B
C
D
A
B
C
D
NOTE:
- Unit not designed to have overhead obstruction.

Table of Contents

Related product manuals