27
7 - POSITIONING AND INSTALLATION
7.7 - Recommended service clearance
Important: This is the minimum space required for maintenance operations and access inside the unit. Depending on the assembly
selected for the unit and the characteristics of the installation site, a larger space around it may be required to ensure proper air
circulation and therefore the correct operation of the unit.
50FF/FC 020-028-037-040-045-047: B1, B2 and BF assemblies
A
B
C
D
A
B
C
D
50FF/FC 020-028-037-040-045-047: BW assembly
50FF/FC 020-028-037-040-045-047: B3, BX, BP and BA assemblies
50FF/FC 020-028-037-040-045-047: BT and BB assemblies
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.225 1.750 1.230 1.200 1.000 1.000 1.600
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.230 1.755 1.905 1.200 1.000 1.000 1.600
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.230 1.760 1.975 1.200 1.000 1.000 1.600
50FF/FC
Overall dimension (mm) Service clearance (mm)
Length Width Height A B C D
020 to 047 2.230 2.565 1.905 1.200 1.000 1.000 1.600
A
B
C
D
A
B
C
D
NOTE:
- Unit not designed to have overhead obstruction.