10
5 - HANDLING
Correct lifting mode
6 - OPERATION LIMITS
(1) With a condensation pressure control disabled operation up to
+12ºC.
(2) When the outdoor temperature is usually below 5ºC WB, the
installation of a support element is recommended.
(3) Operation up to -18ºC WB at partial load
Inlet air conditions
Cooling Heating
50FF 50FC 50FC
Indoor
coil
Minimum temperature 9,7ºC WB 10ºC
Maximum temperature 24ºC WB 27ºC
Outdoor
coil
Minimum temperature -10ºC (1) -15ºC WB (2) (3)
Maximum temperature 52ºC 48ºC 15ºC WB
7 - POSITIONING AND INSTALLATION
7.1 - Storage
Important: It is prohibited to store and install the machine in an
explosive atmosphere zone (ATEX).
If it is necessary to store the unit for a period of time before its
installation, the following recommendations should be followed:
Do not remove the protective packaging and the transport
supports. The unit packed with plastic protective lm should not
remain exposed to the sun for long, as prolonged exposure of
the protective lm can deteriorate the unit’s paint.
Store the unit on a at and horizontal surface.
It is highly recommended to store the unit in a dry place and
protected from the weather.
Supplied accessories must be stored in a dry and clean place
for future unit assembly.
The unit should always be stored under the following
environmental conditions:
- Minimum ambient temperature: -30°C
- Maximum ambient temperature: 50°C
- Maximum relative humidity: 95% (to avoid condensation)