EasyManua.ls Logo

Carrier 50GCQ Series - Reversing Valve Control; Compressor Control; Auxiliary (Electric) Heat Control

Carrier 50GCQ Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
Fig. 31 — Defrost Control Board Location — 50GCQ*04-06 Electro-Mechanical Units
Reversing Valve Control
The DFB has 2 outputs for unit reversing valve control. Operation
of the reversing valves is based on internal logic; this application
does not use an “O” or “B” signal to determine reversing valve po-
sition. Reversing valves are energized during the cooling stages
and the defrost cycle and de-energized during heating cycles.
Once energized at the start of a cooling stage, the reversing valve
will remain energized until the next heating cycle demand is re-
ceived. Once de-energized at the start of a Heating cycle, the re-
versing valves will remain de-energized until the next cooling
stage is initiated.
Compressor Control
The DFB receives inputs indicating Stage 1 Cooling, Stage 2
Cooling and Stage 1 Heating from the space thermostat or unit
control system (SystemVu
controller or RTU Open controller); it
generates commands to start compressors with or without revers-
ing valve operation to produce Stage 1 Cooling (one compressor
runs), Stage 2 Cooling (both compressors run) or Stage 1 Heating
(both compressors run).
Auxiliary (Electric) Heat Control
The 50GCQ unit can be equipped with one or 2 auxiliary electric
heaters, to provide a second stage of heating. The DFB will ener-
gize this Heating System for a Stage 2 Heating Command (heaters
operate concurrently with compressor(s) in the Stage 1 Heating
cycle), for an Emergency Heating sequence (compressors are off
and only the electric heaters are energized) and also during the De-
frost cycle (to eliminate a “cold blow” condition in the space).
Table 7 — 50GCQ Defrost Board I/O and Jumper Configurations
a,b
POINT NAME TYPE OF I/O CONNECTION PIN NUMBER UNIT CONNECTION NOTE
INPUTS
G Fan DI, 24 vac P2-3 CTB-G
Y1 Cool 1 DI, 24 vac P2-5 CTB-Y1
Y2 Cool 2 DI, 24 vac P2-4 CTB-Y2
W1 Heat 1 DI, 24 vac P2-7 CTB-W1
W2 Heat 2 DI, 24 vac P2-6 CTB-W2
R Power 24 vac P3-1 CONTL BRD-8
C Common 24 vac P3-2 CONTL BRD-4
DFT 1 DI, 24 vac DFT-1 to DFT-1
DFT 2 DI, 24 vac DFT-2 to DFT-2
OUTPUTS
IFO Fan On DO, 24 vac P3-9 REHEAT/HP-2
OF OD Fan On DO, 24 vac OF OFR
RVS1 DO, 24 vac P3-7 to P3-5 Energize in COOL
RVS2 DO, 24 vac P3-6 to P3-4 Energize in COOL
COMP 1 DO, 24 vac P3-10 FPT1-REHEAT/HP-6
COMP 2 DO, 24 vac P3-8 FPT2-REHEAT/HP-8
HEAT 2 DO, 24 vac E-HEAT TB4-1
COM 24 vac P3-3 TB4-3
CONFIGURATION
Select Jumper 24 vac P1-1
SPEED-UP CONFIGURATION
Speed-Up Jumper —JMP17—
Speed-Up Jumper —JMP18—
NOTE(S):
a. Jumper for 1-3 seconds: Factory Test — The defrost interval timing is reduced by a factor of 0.1 seconds/minute based on the positions of DIP switches SW1 and SW2
(i.e., 90 minutes will be reduced to 9 seconds).
b. Jumper for 5-20 seconds: Forced Defrost — Defrost runs for 30 seconds if DFT2 is open.

Table of Contents

Related product manuals