GUIDE SPECIFICATIONS (CONT)
4. Filter Rack Kit:
Shall provide filter mounting for downflow applications.
5. Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
6. Low Ambient Package:
Shall consist of a solid--state control and condenser coil
temperature sensor for controlling condenser-- fan motor op-
eration, which shall allow unit to operate down to 0_F
(17.7_C) outdoor ambient temperature when properly
installed.
7. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year-- round
ventilation.
8. Square--To -- Round Duct Transitions (24--48 size):
Shall have the ability to convert the supply and return open-
ings from rectangular to round.
9. Time Guard II
Automatically prevents the compressor from restarting for
at least 4 minutes and 45 seconds after shutdown of the
compressor. Not required when a corporate programmable
thermostat is applied.