79
APPENDIX A — LOCAL DISPLAY AND CCN TABLES
MODE — INPUTS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
INPUTS STATUS DISPLAY
STAT Thermostat Inputs UINPUT
Y1 Thermostat Y1 Input Off/On Y1 forcible
Y2 Thermostat Y2 Input Off/On Y2 forcible
W1 Thermostat W1 Input Off/On W1 forcible
W2 Thermostat W2 Input Off/On W2 forcible
G Thermostat G Input Off/On G forcible
GEN.I General Inputs
FIL.S Filter Status Switch Clean/Dirty FILTSTAT forcible
FAN.S Fan Status Switch Off/On FAN_STAT forcible
FDWN Fire Shutdown Switch Off/On FIREDOWN forcible
ENTH Outdoor Enthalpy Switch Low/High ENTHALPY forcible
RM.OC Remote Occupancy Switch Off/On REM_OCC forcible
HUM Space Humidity Switch Low/High HUM_STAT forcible
IGC.F IGC Fan Request Off/On IDF_FDBK
AIR.Q Air Quality Inputs
IAQ.S IAQ Level (switch) Low/High IAQIN forcible forcible
IAQ IAQ Level (sensor) xxxx IAQ forcible forcible
OAQ OAQ Level (sensor) xxxx OAQ forcible forcible
SP.RH Space Humidity Sensor xxx.x % SPRH forcible forcible
MODE — OUTPUTS
ITEM EXPANSION RANGE UNITS
CCN TABLE/
S u b --- T A B L E
CCN POINT
CCN WRITE
STATUS
DISPLAY WRITE
STATUS
OUTPUTS STATUS DISPLAY
FANS Fan Outputs UOUTPUT
F.SPD Commanded Fan Speed xxx % FANSPEED
IDF.1 Indoor Fan Speed Relay 1 Off/On IDF_1
IDF.2 Indoor Fan Speed Relay 2 Off/On IDF_2
IDF.3 Indoor Fan Speed Relay 3 Off/On IDF_3
COOL Cool Outputs
CMP.A Circuit A Compressor Off/On COMP_A
CMP.B Circuit B Compressor Off/On COMP_B
CRC Cool--->Reheat1 Control Off/On CRC
RH2.A Reheat2 Valve A Off/On RH2_A
RH2.B Reheat2 Valve B Off/On RH2_B
HEAT Heat Outputs
HT.1 Heat Stage 1 Relay Off/On HEAT_1
HT.2 Heat Stage 2 Relay Off/On HEAT_2
ECON Economizer Outputs
EC.CP
Econo Commanded Posi-
tion
0 to 100 % ECONOCMD forcible forcible
EC.AP Econo Actual Position 0 to 100 % ECONOPOS
PE.1 Power Exhaust 1 Relay Off/On PE_1 forcible
PE.2 Power Exhaust 2 Relay Off/On PE_2 forcible
ALRM Alarm Relay Off/On ALM OUT forcible
MODE — SET POINTS
ITEM EXPA NSION RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT
SETPOINT CONFIGURATION
SETPOINTS SET_PNT
OCSP Occupied Cool Setpoint 55 to 80 _F 78 OCSP
UCSP Unoccupied Cool Setpoint 65 to 95 _F 85 UCSP
OHSP Occupied Heat Setpoint 55 to 80 _F 68 OHSP
UHSP Unoccupied Heat Setpoint 40 to 80 _F 60 UHSP
GAP Heat--- Cool Setpoint Gap 2to10 ^F 5 HCSP_GAP
STO.R SPT Offset Range (+/--- ) 0to5 ^F 5 SPTO_RNG
RH.SP Space RH Occupied SP 30 to 100 % 50 SPRH_SP
RH.UN Space RH Unoccupied SP 30 to 100 % 80 SPRH_USP
RH.DB Space RH Deadband 2to20 % 8 SPRH_DB
RH.HB Reheat Heat SP Deadband --- 5 t o 5 ^F 2 RH_HSPDB
LCSP Low Cool SAT Setpoint 55 to 75 _F 55 (03--- 07)
65 (08--- 28)
LCSASP
HCSP H igh Cool SAT Setpoint 50 to 70 _F 55 HCSASP
ComfortLINK v1.X