APPENDIX A — LOCAL DISPLAY AND CCN TABLES
MODE — CONFIGURATION
ITEM EXPANSIO N RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT
PAGE
NO.
CONFIGURATION SERVICE
CONFIGURATION
DISP Dis p l ay Conf i gu r ation DISPLAY
METR Metric Display Off/On Off DISPUNIT 14
LANG Language Selection 0=English
1=Spanish
2=French
3=Portuguese
0 LANGUAGE 14
PROT Password Enable Disable/Enable Enable PAS S_ EBL 14
PSWD Service Password 0000 to 9999 1111 PASSWORD 14
TEST Test Display LEDs Off/On Off (display only,
not in table)
DISPTEST 14
UNIT Unit Configuration UNIT
S.DLY S tartu p Delay 10 to 600 sec 30 STARTDLY 14
U.CTL Unit Control Type 2=Thermostat
3=Space Sensor
2 CTL_TYPE 14
T. C T L Thermostat Control Type 0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0 STATTYPE 14
FN.SW Fan S tatu s S wi tc h 0=No Switch
1=Normal Open
2=Normal Closed
0 FANSTCFG 14
FL.SW Filter Status Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 FILSTCFG 14
FS.SW Fire Shutdown Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
SHTDNCFG 14
RM.SW Remote Occ upancy Swi tc h 0=No Switch
1=Normal Open
2=Normal Closed
0 REMOCCFG 14
SAT.T SA T Settling Time 10 to 900 sec 240 SAT_SET 14
RAT.S RAT Sensor Installed No/Yes No RAT_SENS 14
RH.S RH Sensor on OAQ Input No/Yes No RH_OAQ 14
RH.SW Space Humidity Switch 0=No Switch
1=Normal Open
2=Normal Closed
0 : n o H u m i d i --- M i Z e r F I O P
1 : H u m i d i --- M i Z e r F I O P
HUMSTCFG 14
TCS.C Temp Cmp S trt Cool Fac tr 0to60 mins 0 TCSTCOOL 14
TCS.H TempCmpStrtHeatFactr 0to60 mins 0 TCSTHEAT 14
I.FAN INDOOR FAN CON FIG FAN_CFG
FTYP Indoor F an Type 0 = 1 --- S P E E D
1=LEN VFD
2=ECM
3=DI VFD
4=AI VFD
0
1: SAV option
FAN_TYPE 16
NSPD Num ber of Speeds 2=TWO
3=THREE
7=SEVEN
2 NUM_SPDS 16
OC.FN FanOnWhenOccupied No/Y es Yes OCC_FAN 16
IDF.F Shut Down on IDF Failure No/Yes Yes FAT ALFAN 16
FS.MX Supply Fan Maximum
Speed
80 to 100 100 SPEEDMAX 17
FS.VN Fan Speed --- V entilation 0 to 100 % 67 FSPDVENT 17
FS.AQ Fan Speed --- IAQ Override 0 to 100 % 100 FSPDAQOR 17
FS.E1 Fan Speed --- Free Cool Lo 0 to 100 % 67 FSPDECO1 17
FS.CL Fan Speed --- Mec h Coolin g 60 to 100 % 67 FSPDCOOL 17
FS.RH F an S peed --- Reheat2 65 to 100 % 100 FSPDREHT 17
S.VFD SUPPLY FAN VFD CONFIG 91
N.VLT VFD1 Nom in al M otor Volts 0 to 999 volts 208: 208/230v 1ph or 3ph
460: 460v
575: 575v
VFD1NVLT
N.AMP VFD1 Nomi n al Motor Am p s 0 to 999 amps Motor Dependent VFD1NAMP
N.FRQ V FD1 Nom in al Motor Freq 10 to 500 60 VFD1NFRQ
N.RPM VFD1 Nom in al M otor RPM 50 to 30000 Motor Dependent VFD1NRPM
N.PWR VFD1 Nomi n al Motor HPwr 0 to 500 Motor Dependent VFD1NPWR
M.DIR VFD1 Motor Dir ec tion 0=FORWARD
1=REVERSE
0 VFD1MDIR
ACCL VFD1 Acceleration Time 0 to 1800 secs 30 VFD1ACCL
DECL VFD1 Deceleration Time 0 to 1800 secs 30 VFD1DECL
SW.FQ VFD1 Switching Frequency 0to3 2 VFD1SWFQ