Table 4 — Evaporator-Fan Motor Data
UNIT
50HJ
MAXIMUM
CONTINUOUS
BHP*
MAXIMUM
OPERATING
WATTS*
UNIT
VOLTAGE
MAXIMUM
AMP
DRAW
008,
009
2.90 2615
208/230 7.9
460 3.6
575 3.6
012,
014 Alt
4.20 3775
208/230 12.6
460 5.7
575 5.7
014
Std
5.25 4400
208/230 15.0
460 7.4
575 7.4
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that
the full horsepower and watts range of the motors can be used with
confidence. Using the fan motors up to the ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
Table 5 — Fan Rpm at Motor Pulley Settings*
UNIT
50HJ
MOTOR PULLEY TURNS OPEN
0
1
⁄
2
11
1
⁄
2
22
1
⁄
2
33
1
⁄
2
44
1
⁄
2
55
1
⁄
2
6
008,009 1085 1060 1035 1010 985 960 935 910 890 865 840
012,014 Alt 1080 1060 1035 1015 990 970 950 925 905 880 860 — —
014 Std 1260 1220 1185 1155 1130 1100 1075 1045 1015 990 960 930 900
*Approximate fan rpm shown.
Table 6 — Fan Performance, 50HJ008 — Vertical Discharge Units
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2250 511 0.52 592 0.74 659 0.95 722 1.19 778 1.43 829 1.68
2300 518 0.55 599 0.77 665 0.98 727 1.22 783 1.47 834 1.72
2400 534 0.61 613 0.84 677 1.06 738 1.30 794 1.55 844 1.81
2500 549 0.67 627 0.90 690 1.14 750 1.38 805 1.64 855 1.91
2550 557 0.71 633 0.94 697 1.18 756 1.42 811 1.69 861 1.96
2600 565 0.74 639 0.97 703 1.22 761 1.46 816 1.74 866 2.01
2700 581 0.81 652 1.04 717 1.31 773 1.55 827 1.83 878 2.12
2800 597 0.89 665 1.12 733 1.40 786 1.66 839 1.93 889 2.23
2900 613 0.97 679 1.20 745 1.50 799 1.76 850 2.04 900 2.34
3000 629 1.06 694 1.29 759 1.59 812 1.88 862 2.15 911 2.46
3100 646 1.15 709 1.39 772 1.70 825 1.99 875 2.28 923 2.58
3200 662 1.25 724 1.50 785 1.80 840 2.11 887 2.41 934 2.71
3300 679 1.35 740 1.61 798 1.91 854 2.24 900 2.54 946 2.85
3400 696 1.46 756 1.73 811 2.02 868 2.37 914 2.69 959 3.00
3500 712 1.57 771 1.85 824 2.14 881 2.50 928 2.84 971 3.16
3600 729 1.69 787 1.98 839 2.21 894 2.64 942 2.99 984 3.22
3700 746 1.85 803 2.12 854 2.42 907 2.78 956 3.15 997 3.49
3750 755 1.89 811 2.20 862 2.49 914 2.85 963 3.23 — —
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2250 884 1.97 937 2.33 947 2.66 1022 3.10
2300 885 2.00 939 2.36 979 2.69 1025 3.12
2400 892 2.08 944 2.40 987 2.76 1039 3.20
2500 902 2.18 949 2.48 1002 2.84 1041 3.25
2550 908 2.24 953 2.53 1003 2.87 1045 3.28
2600 913 2.29 957 2.58 1004 2.91 1050 3.31
2700 924 2.40 967 2.70 1010 3.01 1056 3.37
2800 935 2.52 978 2.62 1019 3.13 1061 3.47
2900 946 2.65 989 2.96 1030 3.27 — —
3000 957 2.78 1000 3.09 1040 3.41 — —
3100 968 2.91 1011 3.24 ————
3200 980 3.04 1022 3.38 ————
3300 991 3.18 ——————
3400 1003 3.32 ——————
3500 1014 3.48 ——————
3600 ————————
3700 ————————
3750 ————————
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 6.)
2. indicates field-supplied motor and drive are required.
3. Maximum continuous bhp is 2.90. Extensive motor and electrical
testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the rat-
ings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
7. Interpolation is permissible. Do not extrapolate.
18