Table 7 Fan Performance, 50HJ009 Vertical Discharge Units
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2550 557 0.71 633 0.94 697 1.18 756 1.42 811 1.69 861 1.96
2600 565 0.74 639 0.97 703 1.22 761 1.46 816 1.74 866 2.01
2700 581 0.81 652 1.04 717 1.31 773 1.55 827 1.83 878 2.12
2800 597 0.89 665 1.12 733 1.40 786 1.66 839 1.93 889 2.23
2900 613 0.97 679 1.20 745 1.50 799 1.76 850 2.04 900 2.34
3000 629 1.06 694 1.29 759 1.59 812 1.88 862 2.15 911 2.46
3100 646 1.15 709 1.39 772 1.70 825 1.99 875 2.28 923 2.58
3200 662 1.25 724 1.50 785 1.80 840 2.11 887 2.41 934 2.71
3300 679 1.35 740 1.61 798 1.91 854 2.24 900 2.54 946 2.85
3400 696 1.46 756 1.73 811 2.02 868 2.37 914 2.69 959 3.00
3500 712 1.57 771 1.85 824 2.14 881 2.50 928 2.84 971 3.16
3600 729 1.69 787 1.98 839 2.27 894 2.64 942 2.99 984 3.32
3700 746 1.82 803 2.12 854 2.42 907 2.78 956 3.15 997 3.49
3750 755 1.89 811 2.20 862 2.49 914 2.85 963 3.23
3800 763 1.95 819 2.27 869 2.56 920 2.92 970 3.31
3900 780 2.09 835 2.42 884 2.72 933 3.07 983 3.48
4000 796 2.23 851 2.56 900 2.89 946 3.23 ————
4100 813 2.39 867 2.74 915 3.06 960 3.40 ————
4200 830 2.55 883 2.91 931 3.24 ——————
4250 839 2.63 892 3.00 939 3.34 ——————
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2550 908 2.24 953 2.53 1003 2.87 1045 3.28
2600 913 2.29 957 2.58 1004 2.91 1050 3.31
2700 924 2.40 967 2.70 1010 3.01 1056 3.37
2800 935 2.52 978 2.62 1019 3.13 1061 3.41
2900 946 2.65 989 2.96 1030 3.27
3000 957 2.78 1000 3.09 1040 3.41
3100 968 2.91 1011 3.24 ————
3200 980 3.04 1022 3.38 ————
3300 991 3.18 ——————
3400 1003 3.52 ——————
3500 1014 3.48 ——————
3600 ————————
3700 ————————
3750 ————————
3800 ————————
3900 ————————
4000 ————————
4100 ————————
4200 ————————
4250 ————————
LEGEND
Bhp Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 6.)
2. indicates field-supplied motor and drive are required.
3. Maximum continuous bhp is 2.90. Extensive motor and electrical
testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the rat-
ings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
7. Interpolation is permissible. Do not extrapolate.