Table 15 -- Accessory/FlOP Static Pressure (in. wg)
UNIT
50HJ
015, 017
HEATER
RATED
VOLTAGE*
208/240-3-60
480-3-60
575-3-60
CFM
3,750
4,000
5,000
6,000
7,200
7,500
3,750
4,000
5,000
6,000
7,200
7,500
3,750
4,000
5,000
6,000
7,200
7,500
0.05 (14/19, 26/34)
0.05 (14/19, 26/34)
0.07 (14/19, 26/34)
0.09 (14/19, 26/34)
0.11 (14/19, 26/34)
0.12 (14/19, 26/34)
0.05 (16, 32)
0.05 (16, 32)
0.07 (16, 32)
0.09 (15, 32)
0.11 (15, 32)
0.12 (15, 32)
ELECTRIC HEATERS
PRESSURE DROP
(kW)
0.06 (42/56)
0.06 (42/56)
0.08 (42/56)
0.12 (42/56)
0.16 (42/56)
0.17 (42/56)
0.06 (55)
0.06 (55)
0.08 (85)
0.12 (55)
0.16 (85)
0.17 (55)
0.06 (37)
0.06 (37)
0.08 (37)
0.12 (37)
0.16 (37)
0.17 (37)
LEGEND
0.07 (56/75)
0.07 (56/75)
0.10 (56/75)
0.15 (56/75)
0.20 (56/75)
0.21 (66/76)
0.07(80)
0.07(80)
0.10(80)
0.15 (80)
0.20 (80)
0.21 (80)
ECONOMIZER
PRESSURE
DROP
0.03
0.04
0.05
0.07
0.09
0.10
0.03
0.04
0.05
0.07
0.09
0.10
0.03
0.03
0.05
0.07
0.09
0.10
FlOP -- Factory-Installed Option 3.
*There are no electric heaters available for 017 676-v units.
NOTES:
1. Heaters are rated at 240 v, 480 v, and 676 v.
2. The factory assembled horizontal adapter substantially
improves fan performance.
The static pressure must be added to external static pressure.
The sum and the evaporator entering-air cfm should then be
used in conjunction with the Fan Performance table to deter-
mine blower rpm, bhp, and watts.
Table 16- MoistureMi$er TM Dehumidification
Package Static Pressure Drop (in. wg)
UNIT SIZE UNIT NOMINAL CFM PER TON
50HJ TONS 300 400 500
015 12 .026 .045 .071
017 15 .040 .071 .111
Table 17 -- Fan Rpm at Motor Pulley Settings*
50HJ (No. Turns Open) 0 1/2 1 11/2 2 21/2 3 31/2
015 (208/230, 460, 575 v)t 1147 1124 1101 1078 1055 1032 1010 987
015 (208/230, 460 v)** 1315 1292 1269 1248 1223 1200 1178 1155
017t tt 1-1- tt 1-1- 1021 1002 984 965
017"* tt tf tt tf 1200 1178 1156 1134
*Approximate fan rpm shown.
tlndicates standard drive package.
**Indicates alternate drive package.
ttDue to belt and pulley style, pulley cannot be set to this number of turns open.
4 41/2 5 51/2 6
964 941 918 895 tt
1132 1109 1086 1063 1040
947 928 910 891 873
1112 1091 1069 1047 1025
Table 18- Evaporator Fan Motor Specifications
UNIT NOMINAL MAX EFE MAX MAX MAX
50HJ HP VOLTAGE WATTS % BHP BkW AMPS
015 2.9 208 2700 85.8 3.13 2.34 9.46
(Standard 2.9 230 2700 85.8 3.13 2.34 8.6
2.9 460 2700 85.8 3.13 2.34 4.3
Motor) 3 575 3065 81.7 3.38 2.53 3.9
015 3.7 208 3610 85.8 4.26 3.18 10.5
(Optional 3.7 230 3610 85.8 4.26 3.18 10.5
Motor) 3.7 460 3610 85.8 4.26 3.18 4.8
5 208 5180 87.5 6.13 4.57 15.8
017 5 230 5180 87.5 6.13 4.57 15.8
5 460 5180 87.5 6.13 4.57 7.9
5 575 5180 87.5 6.13 4.57 6.0
LEGEND
BHP -- Brake Horsepower
32