Fig. 2 Dimensions; Sizes 024-036
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Kg/Lb) UNIT HEIGHT (mm/in.) DIMENSION (mm/in.)
Kg Lb A B C D E F
50HS024 400-3-50 128 281 29/64 31/69 44/ 96 24/52 697/27.4 546/21.5
50HS030 400-3-50 136 300 35/78 35/78 53/116 20/43 697/27.4 546/21.5
50HS036 400-3-50 147 324 29/63 42/93 45/100 31/68 798/31.4 648/25.5
UNIT
CENTER OF GRAVITY (mm/in.)
XYZ
50HS024 544/21.4 522/20.5 304/11.9
50HS030 553/20.8 518/20.4 304/11.9
50HS036 552/21.7 531/20.9 344/13.5
REQ’D CLEARANCES FOR SERVICING mm (in.)
Indoor Coil Access Side .....................762(30)
Control Box Access Side ....................762(30)
Unit Top .............................914(36)
Side Opposite Ducts ......................762(30)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L mm (in.)
Unit Top .................................0
Duct Side of Unit ............................0
Side Opposite Ducts ..........................0
Bottom of Unit .............................0
Vertical Discharge, First 305 mm (12 in.) of Supply Duct .....25(1)
LEGEND
CG Center of Gravity
MAT’L Material
REQ’D Required
NOTES:
1. Clearancesmust be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Dimensions in ( ) are in millimeters unless otherwise noted.