Fig. 2 — Dimensions; Sizes 024-036
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Kg/Lb) UNIT HEIGHT (mm/in.) DIMENSION (mm/in.)
Kg Lb A B C D E F
50HS024 400-3-50 128 281 29/64 31/69 44/ 96 24/52 697/27.4 546/21.5
50HS030 400-3-50 136 300 35/78 35/78 53/116 20/43 697/27.4 546/21.5
50HS036 400-3-50 147 324 29/63 42/93 45/100 31/68 798/31.4 648/25.5
UNIT
CENTER OF GRAVITY (mm/in.)
XYZ
50HS024 544/21.4 522/20.5 304/11.9
50HS030 553/20.8 518/20.4 304/11.9
50HS036 552/21.7 531/20.9 344/13.5
REQ’D CLEARANCES FOR SERVICING — mm (in.)
Indoor Coil Access Side .....................762(30)
Control Box Access Side ....................762(30)
Unit Top .............................914(36)
Side Opposite Ducts ......................762(30)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L — mm (in.)
Unit Top .................................0
Duct Side of Unit ............................0
Side Opposite Ducts ..........................0
Bottom of Unit .............................0
Vertical Discharge, First 305 mm (12 in.) of Supply Duct .....25(1)
LEGEND
CG — Center of Gravity
MAT’L — Material
REQ’D — Required
NOTES:
1. Clearancesmust be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Dimensions in ( ) are in millimeters unless otherwise noted.