Fig. 3 Dimensions; Sizes 048,060
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WT CORNER WT (Kg/Lb)
Kg Lb A B C D
50HS048 400-3-50 165 363 38/83 43/95 54/118 30/67
50HS060 400-3-50 168 370 40/89 42/92 48/105 38/84
REQ’D CLEARANCES FOR SERVICING mm (in.)
Indoor Coil Access Side ...................762(30)
Control Box Access Side ..................762(30)
Unit Top ...........................914(36)
Side Opposite Ducts ....................762(30)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L mm (in.)
Unit Top ...............................0
Duct Side of Unit ..........................0
Side Opposite Ducts ........................0
Bottom of Unit ...........................0
Vertical Discharge, First 305 mm (12 in.) of Supply Duct . . . 25 (1)
UNIT
CENTER OF GRAVITY (mm/in.)
XYZ
50HS048 543/21.4 540/21.3 440/17.3
50HS060 493/19.4 539/21.2 440/17.3
LEGEND
CG Center of Gravity
MAT’L Material
REQ’D Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
2. Dimensions in ( ) are in millimeters unless otherwise noted.