19
8 - ELECTRICAL CONNECTION
Customer connection
The following connections must be made on site by the customer:
In this case, it´s possible to install the user terminal on the electrical cabinet.
The power supply of the electrical cabinet (230 V) must be used for terminal power.
The output for general alarm signal is not compatible with the heat recovery coil. With this option, possibility of general alarm upon request.
The outdoor humidity probe (optional) is connected in the same place as the ambient NTC probe. In this case the ambient probe RS485 connected on
the Field-bus will be used.
For a cable section greater than 35 mm
2
, consult the manufacturer.
Up to four RS485 ambient sensors can be connected in series on the eld-bus of the control board.
Mixing box
(option)
Indoor
module
Outdoor
module
1
2
3
4
5
8
6
7
11
12
13
14
15
16
10
9
50NC No. Connections 022 to 028 038 to 042 058 to 086 106 to 118
Package
and Split
versions
1
Main power
supply
400 III (±10%)
Standard unit
Coming soon
5G 25A x 10 mm
2
5G 25A x 10 mm
2
Coming soon
With electrical heaters (optional) 5G 63A x 35mm
2
5G 63A x 35mm
2
2
Remote connection of the graphic terminal (by
default installed on the electrical cabinet)
Telephone cable 6 wires standard (RJ12 connector)
3
Connection of the user terminal (optional)
2 x 1 mm
2
(230V) + 1 shielded cable for communication type AGW20 / 22 (1
braided pair + drain wire + shielding)
4 Remote o /on (optional) 2 x 1 mm
2
5
General alarm signal (optional)
2 x 1 mm
2
6 Remote Cooling/Heating (optional upon request) 2 x 1 mm
2
7
Ambient probe
NTC 2 x 1 mm
2
RS485
4 x 0,5 mm
2
+ shielding
8 Air quality probe (optional) 3 x 1 mm
2
9 Heat recovery coil (optional) 3 x 1 mm
2
10
Connection
of mixing box
(optional)
Standard (BOX3) 5 x 1 mm
2
Enthalpique probe for energy
measurement (BOX-ENT) (opt.)
4 x 0,5 mm
2
+ shielding
Split
version
11
Power supply of
the indoor module
(W96)
Standard unit
Coming soon
4G x 2,5 mm
2
4G x 2,5 mm
2
Coming soon
With electrical heaters (optional) 4G x 10 mm
2
4G x 16 mm
2
12
Control of the
indoor module
(W30)
Standard unit 5 x 1 mm
2
With mixing box (optional) 7 x 1 mm
2
13 Power supply of the indoor fan (230 Vac) (W5) 2 x 1 mm
2
14 Control of the indoor fan (W90) 7 x 1 mm
2
15 Electrical heaters (W37) (optional) 4 x 1 mm
2
16 Heat recovery coil (W53) (optional) 4 x 1 mm
2