WET COIL AIR DELIVERY UNIT 50SZ024--060
230 VOLT
UNIT
SIZE
MOTOR SPEED
EXTERNAL STATIC PRESSURE (IN. WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024
LO
Watts 311 309 304 301 286 ⎯ — — — —
CFM 935 885 820 757 686 — — — — —
MED
Watts — — — — 379 357 357 345 — —
CFM — — — — 957 868 769 647 — —
HI
Watts — — — — — — 447 435 421 —
CFM — — — — — — 970 853 712 —
030
LO
Watts 311 309 304 301 — — — — — —
CFM 935 885 820 757 — — — — — —
MED
Watts 411 405 398 390 379 357 357 — — —
CFM 1195 1155 1100 1028 957 868 769 — — —
HI
Watts — — — — 477 467 447 435 — —
CFM — — — — 1185 1088 970 853 — —
036
LO
Watts 437 433 424 417 403 391 379 362 — —
CFM 1353 1318 1283 1235 1187 1123 1059 975 — —
MED
Watts — — — 531 516 496 478 459 435 —
CFM — — — 1489 1437 1362 1289 1208 1099 —
HI
Watts — — — — — — — 629 602 —
CFM — — — — — — — 1470 1357 —
042
LO
Watts 625 606 586 571 550 534 509 483 457 —
CFM 1539 1496 1466 1437 1387 1330 1264 1183 1093 —
MED
Watts — 741 715 694 669 645 610 4573 544 —
CFM — 1738 1698 1653 1604 1538 1457 1362 1271 —
HI
Watts — — — — — 798 772 738 700 —
CFM — — — — — 1720 1648 1540 1414 —
048
LO
Watts 627 617 607 584 567 548 582 503 — —
CFM 1550 1530 1493 1461 1414 1361 1320 1250 — —
MED
Watts 1771 755 734 711 690 665 639 607 572 —
CFM 1798 1771 1734 1687 1645 1595 1530 1449 1355 —
HI
Watts ⎯ ⎯ 908 887 858 827 804 4767 748 —
CFM ⎯ ⎯ 2000 1944 1876 1811 1735 1647 1555 —
060
LO
Watts 786 769 754 736 722 705 684 658 — —
CFM 2027 1960 1901 1821 1759 1693 1616 1513 — —
MED
Watts 873 849 833 815 798 782 763 748 — —
CFM 2095 2026 1962 1887 1817 1748 1679 1583 — —
HIGH
Watts 1012 993 981 963 948 927 904 886 — —
CFM 2109 2036 1963 1886 1812 1729 1647 1646 — —
*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter an d electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occuratair-
flows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
3. Deduct 10% for 208v.
FILTER PRESSURE DROP (in. wc)
UNIT SIZE
FILTER
SIZEX1
(in.)
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
024,030 20 x 20 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 — — — — — — —
036 20 x 24 — — — — 0.09 0.10 0.11 0.13 0.14 0.15 0.16
042--060 24 x 30 — — — — — — — 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18