APPLICATION DATA
Condensatetrap A2--in.condensatetrap must be fieldsupplied.
1” (25mm) MIN.
2” (50mm) MIN.
TRAP
OUTLET
C99013
Ductwork Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
To convert a unit to downflow discharge Units are equipped
with factory--installed inserts in the downflow openings. Remove
the inserts similar to removing an electrical knockout.
Maximum cooling airflow To minimize the possibility of con-
densate blow --off from the evaporator, airflow through the units
should not exceed 450 cfm/ton.
Minimum cooling airflow The minimum cooling airflow is 350
cfm/ton.
Minimum cooling ambient operating temperature All stan-
dard units have a minimum ambient operating temperature of 40_F
(4.4_C). With accessory low ambient temperature kit, units can op-
erate at temperatures down to 0_F ( -- 17.7_C).
50SZ