Space Sensors--
The PremierLink controller is factory-shipped confgured
for Space Sensor Mode. A Carrier T-55 or T-56 space
sensor must be used. T-55 space temperature sensor
provides a signal of space temperature to the PremierLink
control. T-56 provides same space temperature signal plus
it allows for adjustment of space temperature setpoints
from the face of the sensor by the occupants.
,C,h
©
\
C08201
CCN COM
SENSOR WIRING
Fig. 41 - T-55 Space Temperature Sensor Wiring
Connect T-55: See Fig. 41 for typical T-55 internal
connections. Connect the T-55 SEN terminals to TB1
terminals 1 and 3 (see Fig. 42).
TB1 PL
C08212
Fig. 42 - PremierLink T-55 Sensor
Connect T-56: See Fig. 43 for T-56 internal connections.
Install a jumper between SEN and SET terminals as
illustrated. Connect T-56 terminals to TB1 terminals 1, 3
and 5 (see Fig. 44).
SEN S_
oLK
(T56) ,_
(n)
o
CCN COM
SENSOR WIRING
JUMPER
-_ TERMINALS
AS SHOWN
\ \
\';
Fig. 43 - T-56 Internal Connections
C08202
TB1 PL
TB1 PL
"i.,t-.---j um per
Fig. 44 - PremierLink T-56 Sensor
C08213
Connect Thermostat --
A 7-wire thermostat connection requires a 24-v power
source and a common connection. Use the R and C
terminals on the CTB's THERMOSTAT connection strip
for these. Connect the thermostat's Y1, Y2, W1, W2 and
G terminals to PremierLink TB1 as shown in Fig. 45.
If the 50TC unit is equipped with factory-installed smoke
detector(s), disconnect the factory BLU lead at TB1-6
(Y2) before connecting the thermostat. Identify the BLU
lead originating at CTB-DDC-1; disconnect at TB1-6
and tape oft'. Confirm that the second BLU lead at TB1-6
remains connected to PremierLink J4-8.
SPACE CTB
THERMOSTAT THERMOSTAT
(Z) %
TB1 PL
CX) -%
(E) -D
(EC, -%
Cg> .@
THERMOSTAT
Fig. 45 - Space Thermostat Connections
C08119
If the 50TC unit has an economizer system and
free-cooling operation is required, a sensor representing
Return Air Temperature must also be connected
(feld-supplied and installed). This sensor may be a T-55
Space Sensor (see Fig. 41) installed in the space or in the
return duct, or it may be sensor PNO 33ZCSENSAT,
installed in the return duct. Connect this sensor to TBI-1
and TB1-3 per Fig. 42.
Configure the Unit for Thermostat Mode --
Connect to the CCN bus using a CCN service tool and
navigate to PremierLink Configuration screen for Operating
Mode. Default setting is Sensor Mode (value 1). Change the
value to 0 to reconfigure the controller for Thermostat Mode.
When the PremierLink is configured for Thermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).