EasyManua.ls Logo

Carrier 50TC-D30 User Manual

Carrier 50TC-D30
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
50TC*17- 30
Nominal 15 to 27.5 Tons
With Puron ® (R-410A) Refrigerant
Service and Maintenance Instructions
TABLE OF CONTENTS
TABLE OF CONTENTS 1.........................
SAFETY CONSIDERATIONS 1....................
UNIT ARRANGEMENT AND ACCESS 3...........
SUPPLY FAN (BLOWER) SECTION 4..............
STAGED AIR VOLUME (SAV) CONTROL: 2SPEED
FAN WITH VARIABLE FREQUENCY DRIVE (VFD) 6
ADDITIONAL VFD INSTALLATION AND
TROUBLESHOOTING 7..........................
CONDENSER COIL SERVICE 8...................
EVAPORATOR COILS 10.........................
HIMIDIMIZER DEHUMIDIFICATION SYSTEM 12
THERMOSTATIC EXPANSION VALVE (TXV) 17....
PURON (R410A) REFRIGERANT 19.............
COOLING CHARGING CHARTS 20................
COMPRESSORS 24..............................
TROUBLESHOOTING THE COOLING SYSTEM 26..
CONVENIENCE OUTLETS 27....................
SMOKE DETECTORS 28.........................
INDICATORS 34................................
PROTECTIVE DEVICES 35.......................
PREMIERLINK CONTROL 36...................
RTUOPEN CONTROL SYSTEM 38................
ECONOMI$ER SYSTEMS 40......................
PRESTARTUP/STARTUP 49....................
STARTUP, PREMIERLINK CONTROLS 50.......
STARTUP, RTUOPEN CONTROLS 51............
FASTENER TORQUE VALUES 51.................
APPENDIX I. MODEL NO. NOMENCLATURE 52...
APPENDIX II. PHYSICAL DATA 53................
APPENDIX III. FAN PERFORMANCE 61...........
APPENDIX IV. WIRING DIAGRAMS 67............
APPENDIX V. MOTORMASTER SENSOR
LOCATIONS 80.................................
UNIT START-UP CHECKLIST 81..................
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install, repair, or service air-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguishers available for all brazing
operations.
Follow all safety codes. Consult local building codes and
National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safetyalert
symbol . When you see this symbol on the unit and in
instructions or manuals, be aware of the potential for
physical injury hazards.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safetyalert
symbol. DANGER identifies a hazardous situation which,
if not avoided, will result in death or severe personal
injury. WARNING indicates a hazardous situation which,
if not avoided, could result in death or personal injury.
CAUTION indicates a hazardous situation which, if not
avoided, could result in minor to moderate injury or
product and property damage. NOTICE is used to address
practices not related to physical injury. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
Question and Answer IconNeed help?

Do you have a question about the Carrier 50TC-D30 and is the answer not in the manual?

Carrier 50TC-D30 Specifications

General IconGeneral
Model50TC-D30
RefrigerantR-410A
Power Supply208/230V, 1 Phase, 60Hz
Compressor TypeScroll
HSPFNot Applicable
StagesSingle Stage
Heating CapacityNot Applicable
Operating Temperature (Heating)Not Applicable
TypeAir Conditioner
Cooling Capacity30, 000 BTU
Operating Temperature (Cooling)Up to 125°F

Summary

SAFETY CONSIDERATIONS

UNIT ARRANGEMENT AND ACCESS

Routine Maintenance

Lists monthly/quarterly maintenance tasks for the unit.

Seasonal Maintenance

Lists maintenance tasks for the beginning of each season.

SUPPLY FAN (BLOWER) SECTION

Changing Fan Speed

Details how to change fan speed by adjusting the motor pulley.

STAGED AIR VOLUME (SAV) CONTROL: 2-SPEED FAN WITH VARIABLE FREQUENCY DRIVE (VFD)

Staged Air Volume (SAV) Indoor Fan Speed System

Explains the SAV system's function with VFD for airflow control.

ADDITIONAL VFD INSTALLATION AND TROUBLESHOOTING

Refers to supplemental manuals for VFD installation and troubleshooting.

Replacing the Motor

Step-by-step instructions for replacing the belt-driven motor.

CONDENSER COIL SERVICE

Recommended Condenser Coil Maintenance and Cleaning

Outlines recommended procedures for maintaining and cleaning the condenser coil.

Routine Cleaning of Coil Surfaces

Details the use of Totaline® cleaner for routine coil surface maintenance.

EVAPORATOR COILS

Routine Cleaning of Evaporator Coil Surfaces

Details routine cleaning of evaporator coils using Totaline® cleaner.

Totaline® Environmentally Sound Coil Cleaner Application Instructions

Provides step-by-step instructions for applying the coil cleaner.

HIMIDI-MIZER® ADAPTIVE DEHUMIDIFICATION SYSTEM

Humidi-MiZer® Modes

Explains the different operating modes of the Humidi-MiZer system.

Reheat1 (Subcooling Mode) for Units A17 – A30

Explains the Reheat1 (Subcooling) mode for dehumidification.

Reheat2 (Hot Gas Reheat Mode) for A17 – A30

Describes the Reheat2 (Hot Gas Reheat) mode for dehumidification without cooling.

Table 4 - Humidi-MiZer® Troubleshooting

Provides troubleshooting guidance for Humidi-MiZer system issues.

THERMOSTATIC EXPANSION VALVE (TXV)

Replacing TXV

Provides safety precautions and steps for replacing the TXV.

PURON® (R-410A) REFRIGERANT

Refrigerant Charge

Instructions for preparing the unit for refrigerant charge adjustment.

Low-Charge Cooling

Explains low-charge cooling procedures using charging charts.

Using the Cooling Charging Charts

Guides on how to use the cooling charging charts for proper charge.

COOLING CHARGING CHARTS

Displays cooling charging charts for 15 Ton units.

COOLING CHARGING CHARTS (cont.)

Displays cooling charging charts for 25 Ton units.

COMPRESSORS

Replacing the Filter Drier

Step-by-step guide for replacing the filter drier.

TROUBLESHOOTING THE COOLING SYSTEM

Table 5 - Cooling Service Troubleshooting

Provides a table of common cooling system problems, causes, and remedies.

SMOKE DETECTORS

FIOP Smoke Detector Wiring and Response

Explains the wiring and response of the FIOP smoke detector.

Alarm State

Describes what happens when the smoke detector enters the alarm state.

Troubleshooting

Troubleshooting guide for controller and sensor issues.

PROTECTIVE DEVICES

Compressor Protection

Covers overcurrent and overtemperature protection for compressors.

Supply (Indoor) Fan Motor Protection

Details protection devices for the indoor fan motor.

Troubleshooting Supply Fan Motor Overload Trips

Guidance for troubleshooting supply fan motor overload trips.

PREMIERLINK™ CONTROL

RTU-OPEN CONTROL SYSTEM

Additional RTU-OPEN Installation and Troubleshooting

Refers to manuals for RTU-OPEN installation and troubleshooting.

ECONOMISER SYSTEMS

EconoMi$er IV Control Modes

Explains different control modes for the EconoMi$er IV.

Differential Enthalpy Control

Control mode using differential enthalpy sensors.

Indoor Air Quality (IAQ) Sensor Input

Input for IAQ sensor for demand control ventilation.

Demand Control Ventilation (DCV)

Using EconoMi$er IV for demand controlled ventilation.

PRE-START-UP/START-UP

START-UP, GENERAL

General procedures for unit start-up and preparation.

Unit Preparation

Steps for preparing the unit for start-up according to instructions.

Compressor Rotation

How to determine and correct compressor rotation direction.

START-UP, PREMIERLINK™ CONTROLS

START-UP, RTU-OPEN CONTROLS

APPENDIX I. MODEL NUMBER NOMENCLATURE

APPENDIX III. FAN PERFORMANCE

Table 14-50TC*D17 VERTICAL SUPPLY / RETURN

Fan performance data for 15 Ton vertical units.

Table 15-50TC*D20 VERTICAL SUPPLY / RETURN

Fan performance data for 17.5 Ton vertical units.

Table 17-50TC*D28 VERTICAL SUPPLY / RETURN

Fan performance data for 25 Ton vertical units.

Table 18-50TC-D30 VERTICAL SUPPLY / RETURN

Fan performance data for 27.5 Ton vertical units.

Table 19-50TC*D18 HORIZONTAL SUPPLY / RETURN

Fan performance data for 15 Ton horizontal units.

Table 20-50TC*D21 HORIZONTAL SUPPLY / RETURN

Fan performance data for 17.5 Ton horizontal units.

Table 22-50TC*D29 HORIZONTAL SUPPLY / RETURN

Fan performance data for 25 Ton horizontal units.

APPENDIX IV. WIRING DIAGRAMS

Table 25 - Wiring Diagrams

Table listing wiring diagram part numbers by unit size and options.

Fig. 58 – 50TC D30 Control Diagram 208/230–3–60

Control diagram for 208/230V 50TC D30 unit.

Fig. 59 – 50TC D30 Control Diagram – 460/575–3–60

Control diagram for 460/575V 50TC D30 unit.

Fig. 62 – 50TC D17 – D30 Control Diagram 208/230–3–60; 460/575–3–60 with Humidi-MiZer®

Control diagram with Humidi-MiZer for 208/230V and 460/575V units.

Fig. 66 – 50TC – PremierLink™ System Control Wiring Diagram

Wiring diagram for the PremierLink system control.

Fig. 67 – 50TC – RTU-OPEN Wiring Diagram

Wiring diagram for the RTU-OPEN system.

Fig. 68 – 50TC – SAV – VFD System Control Wiring Diagram

Wiring diagram for the SAV-VFD system control.

UNIT START-UP CHECKLIST

II. PRE-START-UP

Checklist of pre-start-up inspections and verifications.

III. START-UP

Checklist for electrical, temperature, pressure, and general start-up checks.

Related product manuals