C10329
'LPHQVLRQV7&.%
C
B
A
D
C08337
6HUYLFH&OHDUDQFH
/2& ',0(16,21 &21',7,21
A
48--- in (1219 mm) Unit disconnect is mounted on panel
18--- in (457 mm) No disconnect, convenience outlet option
18--- in (457 mm) Recommended service clearance
12--- in (305 mm) Minimum clearance
B
42--- in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall)
36--- in (914 mm) Surface behind servicer is electrically non --- conductive (e.g., wood, fiberglass)
Special Check for sources of flue products within 10 --- ft of unit fresh air intake hood
C
36--- in (914 mm) Side condensate drain is used
18--- in (457 mm) Minimum clearance
D
42--- in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36--- in (914 mm) Surface behind servicer is electrically non --- conductive (e.g., wood, fiberglass)
5$.%
$&/5&30'(3"7*5:$(
&85%6:(,*+76',0(16,2167&0'cont
5$.%