Table 4 - Electrical Data (Continued)
RLA LRA RLA LRA Qty HP FLA HP FLA Heater P.N
Application
FLA
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 - - - 23.6 30
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER116A00
9.7 13.9
23.6 30
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER113A00
11.5 16.5
23.9 30
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER114A00
19.3 27.9
38.1 40
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER115A00
22.9 33.1
44.6 45
7.8 51.5 7.8 51.5 1 1 3.4 2.0 2.6 CRHEATER114A00,116A00
29 41.8
55.5 60
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 - 0 0.0 25.4 30
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER116A00
9.7 13.9
25.4 30
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER113A00
11.5 16.5
26.1 30
7.8 51.5 7.8 51.5 1 1 3.4
3.1 4.4 CRHEATER114A00
19.3 27.9
40.4 45
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER115A00
22.9 33.1
46.9 50
7.8 51.5 7.8 51.5 1 1 3.4 3.1 4.4 CRHEATER114A00,116A00
29 41.8
57.8 60
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 - - - 29.5 35
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER116A00
9.7 13.9
29.5 35
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER113A00
11.5 16.5
29.5 35
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER114A00
19.3 27.9
39.1 40
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER115A00
22.9 33.1
45.6 50
9.7 64.0 10.6 74.0 1 1 3.4 2.4 3.4 CRHEATER114A00,116A00
29 41.8
56.5 60
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 - - - 33.5 40
9.7
64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER116A00
9.7 13.9
33.5 40
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER113A00
11.5 16.5
33.5 40
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER114A00
19.3 27.9
44.1 45
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER115A00
22.9 33.1
50.6 60
9.7 64.0 10.6 74.0 1 1 3.4 3.9 7.4 CRHEATER114A00,116A00
29 41.8
61.5 70
Legend and Notes for Electrical Data Table
(AB)
=5v
(BC) 404 - 397 =7v
(AC) 457 - 397 =2v
AB = 392v
BC = 404v Determine Percentage Voltage Imbalance.
AC = 395v
1191 7
3 397
Example: Supply Voltage is 400V - 3Ph - 50Hz
Maximum Deviation From Average Voltage
50TCM Compressor
MCA - Minimum Circuit Amps
Locked Rotor Amps
Unbalanced 3-Phase Supply Voltage
Minimum Voltage: 360V , Maximum Voltage: 440V on 400/3/50
MOCP - Maximum Overcurrent Protection
- Application power at rated power supply voltage
Indoor (Evaporator) Fan Motor
IFM Electric Heater
Unit Size
Full Load Amps
MOCP
Outdoor (Condenser) Fan Motor
Rated Load Amps
D14
Never operate a motor where phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage imbalance
Average Voltage
= 100 X
Determine maximum deviation from average voltage.
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
3
= = 397V
% Voltage
Imbalance
= 100 X = 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
Average Voltage =
392 + 404 + 395 Maximum Deviation is 7v.
Standard
400/3/50
Medium
D12
Standard
400/3/50
Medium
MCA
OFM
No.1 No.2
Drive
package
Indoor Motor
Power
V / Ph / Hz