EasyManua.ls Logo

Carrier 50TCM Series - Page 7

Carrier 50TCM Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
'LPHQVLRQV7&."
C
B
A
D
6HUYLFH&OHDUDQFH
/2& ',0(16,21 &21',7,21
A
48--- in (1219 mm) Unit disconnect is mounted on panel
18--- in (457 mm) No disconnect, convenience outlet option
18--- in (457 mm) Recommended service clearance
12--- in (305 mm) Minimum clearance
B
42--- in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall)
36--- in (914 mm) Surface behind servicer is electrically non --- conductive (e.g., wood, fiberglass)
Special Check for sources of flue products within 10 --- ft of unit fresh air intake hood
C
36--- in (914 mm) Side condensate drain is used
18--- in (457 mm) Minimum clearance
D
42--- in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
36--- in (914 mm) Surface behind servicer is electrically non --- conductive (e.g., wood, fiberglass)
5$."
&85%6:(,*+76',0(16,2167&007 (cont.)
Page 7

Related product manuals