11
instructions included with the cleaner. The optimum
solution temperature is 100°F (38°C).
NOTE: Do NOT USE water in excess of 130°F (54°C), as
the enzymatic activity will be destroyed.
5. Thoroughly apply Totaline Environmentally Sound
Coil Cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, upanddown motion.
Avoid spraying in horizontal pattern to minimize
potential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned
areas.
8. Interior and exterior finned areas must be thoroughly
cleaned.
9. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10minute
saturation is achieved.
11. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
Indoor Coil
Cleaning the Indoor Coil:
1. Turn unit power off. Use proper lockout/tagout
procedures.
2. Remove indoor coil access panel.
3. If economizer or twoposition damper is installed,
remove economizer by disconnecting the Molex®
plug and removing mounting screws.
4. Slide filters out of unit.
5. Clean coil using a commercial coil cleaner or
dishwasher detergent in a pressurized spray canister.
Wash both sides of coil and flush with clean water.
For best results, backflush toward returnair section
to remove foreign material. Flush condensate pan
after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
8. Replace access panels.
Refrigeration System Components:
Each heat pump refrigeration system includes a
compressor, accumulator, reversing valve, dualfunction
outdoor coil with vapor header check valve, cooling liquid
line with a filter drier and a check valve, dualfunction
indoor coil with a vapor header check valve, and heating
liquid line with check a valve and a strainer. Unit sizes
A0407 have a single compressorcircuit; unit sizes D08
through D12 have two compressorcircuits. See Fig. 15
for typical unit piping schematic (unit size D09 (4row
indoor coil) with two compressorcircuits is shown).
Dualfunction outdoor and indoor coils are designed to
provide parallel coil circuits during evaporatorfunction
operation and converging coil circuits during the
condenserfunction operation.
COMPRESSOR
ACCUMULATOR
HPS
COMPRESSOR
ACCUMULATOR
HPS
Filter
Drier
2B
1B
LPS/LOC
Acutrol
DFT 1
Cooling Liquid Lines
DFT 2
2A
1A
1D
2D
Outdoor Coil
Indoor Coil
Comp 2
Comp 1
2C
1C
Strainer
Heating Mode Liquid Lines
Acutrol
C09228
Fig. 15 Typical Unit Piping Schematic (with TXV valves on Indoor Coils)