4
NOTES:
1. Refer to print for roof curb accessory
dimensions.
2. Dimensions in ( ) are in millimeters.
3. Center of Gravity.
4. Direction of airflow.
5. Ductwork to be attached to accessory roof
curb only.
6. Minimum clearance:
•Rear, 7
-0
(2134) for coil removal. This
dimension can be reduced to 4
-0
(1219) if
conditions permit coil removal from the top.
Left side: 4
-0
(1219) for proper condenser
coil airflow.
Front, 4
-0
(1219) for control box access.
Right side: 4
-0
(1219) for proper opera-
tion of damper and power exhaust if so
equipped.
•Top, 6
-0
(1829) to assure proper con-
denser fan operation.
Local codes or jurisdiction may prevail.
7. With the exception of clearance for the con-
denser coil and the damper/power exhaust
as stated in Note #6, a removable fence or
barricade requires no clearance.
8. Dimensions are from outside of corner post.
Allow 0
-
5
/
16
(8) on each side for top cover
drip edge.
9.
A 90 degree elbow must be installed on
the supply ductwork below the unit dis-
charge for units equipped with electric
heaters
.
Fig. 4 — Base Unit Dimensions; 50TJ016
UNIT
STD. UNIT
WEIGHT
ECONOMI$ER
WEIGHT
CORNER
A
CORNER
B
CORNER
C
CORNER
D
DIM ADIM BDIM C
ft-in. (mm)
50TJ016
1560 lbs
708 kg
80 lbs
36.3 kg
392 lbs
178 kg
366 lbs
166 kg
387 lbs
176 kg
416 lbs
188 kg
3-5
(1041)
3-6
(1067)
1-8
(508)