PERFORMANCE AND ELECTRICAL DATA (CONT.)
MODEL 52MQ (265--1-- 60)
MODEL
NUMBER
52MQ
CAPACITY*
EER COP†
VOLTAGE
RANGE
COOLING
Cooling
Heating
AMPS WATTS
Rev. Cyc. Electic
U 0 7 --- --- --- 4 --- ---
SEE POWER
CORD
SELECTION
GUIDE
BELOW
--- ---
239 --- 292
--- ---
U 0 9 --- --- --- 4 9000 8400 10.9 3.5 3.2 825
U 1 2 --- --- --- 4 11,400 10,600 10.8 3 4.2 1050
U 1 5 --- --- --- 4 --- --- --- --- --- ---
MODEL
NUMBER
52MQ
POWER
FACTOR
(%)
FAN MOTOR
R---22
CHARGE
(OZ)
DEHUM.
(Pint/Hr)
SENSIBLE
HEAT
FACTOR
APPROX.
CHASSIS
SHIP WT.
(lb)
In-
door
Mo-
tor
HP
Indoor
Fan
Motor
Full
Load
Amps
Indoor CFM
Outdoor
Motor
HP
Outdoor
Motor
Full
Load
Amps
Low Med High
U 0 7 --- --- --- 4 --- --- --- --- --- --- --- --- --- --- --- 125
U 0 9 --- --- --- 4 97 0.029 0.2 275 285 300 0.06 0.4 29.6 2.7 0.7 125
U 1 2 --- --- --- 4 98 0.029 0.2 220 250 290 0.06 0.4 37.4 4.3 0.66 140
U 1 5 --- --- --- 4 --- --- --- --- --- --- --- --- --- --- --- 150
LEGEND
EER — Energy Ef f iciency Ratio
* Rated in accordance with ARI Standard 380-93.
† Coefficient of Performance (COP) at 47 F ou tdoor ambient temperature.
POWER CORD SELECTION GUIDE
52M PTACs are not individually equipped with a power cord, so one must be ordered separately
based on the voltage and ampeage of your electrical circuit. If the unit is to be plugged into a
receptacle, then a line cord connection kit needs to be selected. If it will be permanently connnected,
a hardwire connection must be used.
Model No. Voltage Receptacle Type Heating (BTUH)
Heater
(Kw)
Input
Power
Current
(Amps)
Branch
Circiut
Full Amps
PWRCORD---265V ---15A
265V
15 amp /250 6826 2 2000 9.6 15
PWRCORD---265V ---20A 20 amp /250 10471 3 3068 14.7 20
P W R C OR D --- 2 6 5 --- 3 0 A 30 amp /250 17116 5 5015 23.8 30
NOTE: In compliance with UL, and the National Electrical Code, 265V units installed iwth a power cord require the use use of a 265V electrical subbase.
RECEPTACLE AND FUSE TYPES
UNIT NAMEPLATE VOLTAGE 265
OUTLET RATED VOLTS/AMPS 277/15 277/20 277/30
OUTLET BLADE CONFIGURATION
RECEPTACLE TYPE A B C
NEMA CONFIGURATION 7 --- 1 5 R 7 --- 2 0 R 7 --- 3 0 R
TIMEDEALYFUSEORHACRCIRCUITBREAKER(AMPS) 15 20 30
LEGEND
HACR --- Heating, Air Conditioning, and Refrigeration
NEMA --- National Electrical Manufacturers Association
New York City Department of Buildings, Material
and Equipment Acceptance — MEA #------ ---- --