10
Circulation Air Blower Data -- 58HDV100
Cooling Adjustment Heating Rise Adjustment
DIP Switch
(OFF = 0
ON = 1)
High Cool @ .50
in wc(125 Pa)
Low Cool (80%
of High Cool)
** Adjust
Jumper
Setting
DIP Switch
(OFF = 0
ON = 1)
High Heat
Rise
Change @
0.20 in wc
(50 Pa)
Low Heat
Rise
Change at
Resultant
Static
5&6 CFM L/s CFM L/s 3&4
00 2108 995 1686 995 + 00 -- 3 -- 3
*00 1974 932 1579 932 *NOM *00 0 0
00 1812 855 1450 855 -- 00 4 5
01 1712 808 1370 808 + 01 1 1
01 1587 749 1270 749 NOM 01 4 5
01 1422 671 1138 671 -- 01 9 10
10 1312 619 1050 619 + 10 -- 2 -- 1
10 1197 565 958 565 NOM 10 1 2
10 1056 498 845 498 -- 10 5 7
11 919 434 735 434 + 11 -- 5 -- 6
11 797 376 638 376 NOM 11 -- 3 -- 3
11 641 303 513 303 -- 11 2 2
Airflow performance includes 1” washable filter media.
*Factory Setting
**Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating
Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is
present with the ”O line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable.
Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls.
Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in ris e).
Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory
default s ettings.
Table 2 Airflow
DIP Switch
(OFF = 0 / ON = 1)
Continuous Fan @
0.10 in wc (25 Pa) ESP
1&2 CFM L/s
*00 1032 487
01 1778 839
10 2178 1028
11 2178 1028
* Factory Setting
Table 3 SW2 DIP Assignments
DIP Switch Blower Parameter
1&2 Cont Fan Adj
3&4 Heat Speed Adj
5&6 Cool Speed Adj
7&8 Cool On/Off Delay
Table 4
Cooling Delay Options (SW2 -- 7, 8)
ON DELAY OFF DELAY
DIP SW2 -- 7/8
(OFF = 0 / ON = 1)
Timed ON (sec)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
delay
*00 5 OFF 90 100%
01 5 OFF 0 OFF
10 30 50% 30 100%
11 30 50% 180 50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1
Airflow resumes to 100% after on delay time is completed
Airflow stops (or switches to continuous fan speed) after off delay time is completed
* Factory Setting
MAX CFM’s for Factory Washable Filters
Filter Size (in/mm) CFM L/s
14 X25 / 356 x 635 1400 661
16 X25 / 406 x 635 1600 755
20 X25 / 508 x 635 2000 944
24 X25 / 610 x 635 2500 1180
Max CFM based on 600 FPM (3.0 M/s)
NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s).
These filters only allow half the airflow when compared to 600 FPM (3.0
M/s) filters.
EXAMPLE (approx.):
20in X 25in @ 600 FPM = 2000 CFM, @ 300 FPM = 1000 CFM
508mm x 635mm @ 3.0 M/s = 944 L/s, @ 1.5 M/s = 472 L/s