EasyManua.ls Logo

Carrier 58MSA - Page 27

Carrier 58MSA
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
d. Permanently attach elbow/perforated disk assembly to
straight portion of pipe using RTV or by cementing. (See
Fig. 35.)
2. Attach combustion-air inlet pipe.
a. Determine location of combustion-air intake pipe connec-
tion to combustion-air intake housing as shown in Fig. 34
for application.
b. Reposition combustion-air intake housing plug fitting in
appropriate unused intake housing connection.
c. Install pipe support (factory-supplied in loose parts bag)
into selected furnace casing combustion-air pipe hole. Pipe
support should be positioned at bottom of casing hole.
d. Insert assembled combustion-air inlet pipe into intake
housing.
e. Make sure elbow is oriented in an acceptable direction and
that the minimum clearance of 3 in. is observed. (See Fig.
34.)
f. Drill a 1/8-in. hole in 2-in. combustion-air inlet pipe using
hole in intake housing as a guide.
g. Install a field-supplied No. 6 or No. 8 sheet metal screw
into combustion-air pipe.
h. Install casing hole filler cap (factory-supplied) in loose
parts bag) in unused combustion-air pipe casing hole.
NOTE: Do not attach combustion-air intake pipe permanently to
combustion-air intake housing since it may be necessary to remove
pipe for service of ignitor or flame sensor.
COMBUSTION-AIR INTAKE HOUSING PLUG
FITTING
The combustion-air intake plug fitting must be installed in
unused combustion-air intake housing. This fitting must be
attached by using RTV sealant, or by drilling a 1/8-in. hole in
fitting, using hole in intake housing as a guide. Install a
field-supplied No. 6 or No. 8 sheet metal screw.
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake
housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting
for use when moisture is found in combustion-air intake pipe
and combustion box. If use of this drain connection is desired,
drill out fittings tap plug with a 3/16-in. drill and connect a
field-supplied 3/8-in. tube. This tube should be routed to open
condensate drain for furnace and A/C (if used), and should be
trapped. (See Fig. 36.)
Fig. 34Combustion-Air and Vent Pipe
Connections
Make sure there is adequate clearance (3-in. minimum) to any
fixed or loose objects in order to ensure an adequate
combustion-air supply. Failure to follow this caution will
result in minor unit operation or performance satisfaction.
A96188
COMBUSTION-
AIR
COMBUSTION-
AIR
AIR
FLOW
VENT
VENT
VENT
AIR
FLOW
AIR
FLOW
AIR
FLOW
UPFLOW DOWNFLOW
HORIZONTAL-LEFT DISCHARGE HORIZONTAL-RIGHT DISCHARGE
Select 1 vent pipe connection and
1 combustion-air pipe connection.
COMBUSTION-
AIR
COMBUSTION-
AIR
COMBUSTION-
AIR
COMBUSTION-
AIR
NOTE: Select 1 vent pipe connection and
1 combustion-air pipe connection.
NOTE:
VENT
VENT
VENT
Fig. 35Combustion-Air Inlet Pipe Assembly
Length of Straight Pipe Portion of
Combustion-Air Inlet Pipe Assembly (In.)
CASING WIDTH A
17-1/2 8-1/2 ± 1/2
21 10-1/2 ± 1/2
24-1/2 12 ± 1/2
A96211
FIELD-SUPPLIED
2-IN. DIAMETER
PVC PIPE
FIELD-SUPPLIED
2-IN. DIAMETER
PVC 90° ELBOW
COMBUSTION-AIR DISC
(FACTORY-SUPPLIED IN
LOOSE PARTS BAG)
A
Fig. 36Air Intake Housing Plug Fitting Drain
A96190
COMBUSTION
AIR PIPE
BURNER
BOX
COMBUSTIONAIR
INTAKE HOUSING
3/8
ID TUBE
TRAP
TO OPEN
DRAIN
3/16
DRILL
HOUSING
PLUG
4
MIN
27

Other manuals for Carrier 58MSA

Related product manuals