PLUG
AUXILIARY 'U" BOX
COLLECTOR BOX
DRAIN TUBE
(BLUE AND WHITE STRIPED)
O
o
CONDENSATE
TRAP
COLLECTOR BOX
TUBE (GREEN)
BOX EXTENSION
DRAtNTUBE
COLLECTOR BOX
EXTENSION TUBE
HOUSING
DRAIN TUBE (VIOLET)
BOX
DRAIN TUBE (BLUE)
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
040,060, AND 080 HEATING INPUT FURNACES
Fig. 10--Horizontal Left Tube Configuration
A00215
CONDENSATE TRAP LOCATION
The condensate tlap must be removed from the factor-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2 or 10.
To relocate condensate trap from the blower shelf to desired
location, perform the Ibllowing:
1. Remove 3 robes connected to condensate trap.
2. Remove tlap flora blower shelf by gently pushing tabs inward
and rotating trap.
3. Install casing hole filler cap (factov-supplied in loose parts
bag) into blower shelf hole where tlap was removed.
-9 CARBON MONOXIDE POISONING HAZARD
Failure to _bllow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated.
4. Install condensate trap into casing hole by inserting tube
connection stubs through casing hole and rotating until tabs
snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (fi_ctory=supplied in loose parts bag)
CONDENSATE TRAP TUBING
NOTE: See Fig. 10 or tube routing label on main fl/rnace door to
check for proper connections.
10
1. Collector Box Drain Tube
a Install &ain tube coupling (factory-supplied in loose parts
bag) into collector box drain tube (blue label) which was
previously connected to condensate trap
b. Connect large diameter drain robe and clamp (factory-
supplied in loose parts bag) to drain robe coupling, extend-
ing collector box &ain robe
c Route extended robe (blue label) to condensate trap and cut
to appropriate length
d. (lamp robe to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
drain robe which was previously connected to condensate
trap.
b. Use inducer housing &ain extension robe (violet label and
factoryosupplied in loose parts bag) to connect LOWER
inducer housing &ain connection to the condensate trap.
c. Detem_ine appropriate length, cuL and connect robe.
d. (lamp robe to prevent any condensate leakage.
3. Relief Port Tube
a. Use smaller diameter robe (factov-supplied in loose parts
bag) to extend collector box tube (green label) which was
previously connected to the condensate trap.
b. Route extended collector box pressure robe to relief port
connection on the condensate trap.
c. Detem_ine appropriate length, cuL and connect robe.
d. (lamp robe to prevent any condensate leakage.