EasyManua.ls Logo

Carrier 58MTA - Page 35

Carrier 58MTA
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Natural gas service pressure must not exceed 0.5 psig (14-in. wc),
and be no less than 0.16 psig (4.5-in. wc).
Thermostat wire connections at R and W/W1 are the minimum
required for gas heating operation. W2 must be connected for
2-stage heating thermostats. C
OM, Y/Y2, and G are required for
cooling, heat pumps, and some clock thermostats. These must be
made at the 24-v terminal block on the control. (See Fig. 32.)
This furnace can be installed with either a single-stage heating or
a 2-stage heating thermostat.
For single-stage thermostats, connect thermostat W to W/W1 at
furnace control terminal block. (See Fig. 27 and 52H.) For
single-stage thermostats, the control will determine, based on
length of previous heating on and off cycles, when to operate in
low- and high- gas heat for optimum comfort. Setup switch-1
(SW-1) must be in the factory-shipped OFF position. See Fig. 31
and Table 9A and B for setup switch information.
If a 2-stage heating thermostat is to be used, move SW-1 to ON
position at end of furnace installation. This overrides built-in
control process for selecting high and low fire and allows the
TABLE 8—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH AND WITHOUT INSULATION IN
WINTER DESIGN TEMPERATURE AMBIENT*
UNIT
SIZE
WINTER DESIGN
TEMPERATURE
(°F)
MAX PIPE
DIAMETER
(IN.)
WITHOUT
INSULATION
WITH 3/8–IN. OR
THICKER INSULATION†
060
20 2 44 70
0 2 21 70
-20 2 20 57
080
20 2 55 55
0 2 30 55
-20 2 16 55
20 2.5 58 70
0 2.5 29 70
-20 2.5 14 67
100
20 2.5 40 40
0 2.5 38 40
-20 2.5 21 40
20 3 63 70
0 3 30 70
-20 3 12 70
120
20 3 70 70
0 3 38 70
-20 3 19 70
20 4 65 70
0 4 26 70
-20 4 5 65
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length
as specified in Table 7.
Insulation thickness based on R value of 3.5 per in.
Fig. 42—Freeze Protection
A93058
32
°
F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
Table 9A—Furnace Setup Switch Description
SETUP
SWITCH
NO.
SWITCH
NAME
NORMAL
POSITION
DESCRIPTION
OF
USE
SW-1
Adaptive
Heat
Mode
OFF
When off, allows 2-stage operation with a
single-stage thermostat.
Turn on when using 2-stage
thermostat to allow Low Heat
operation when R to W/W1 closes
and High Heat operation when
R to W/W1 and W2 close.
SW-2
Blower
OFF
delay
ON or OFF
Control blower OFF
delay time. Used in
conjunction with SW-3.
See Table 9B.
SW-3
Blower
OFF
delay
ON or OFF
Control blower OFF
delay time. Used in
conjunction with SW-2.
See Table 9B.
Table 9B—Blower Off Delay Setup Switch (SW)
2–Stage Units with PSC Blower Motors
DESIRED HEATING MODE
BLOWER-OFF DELAY (SEC)
SETUP SWITCH
SW-2 SW-3
90 OFF OFF
120 OFF ON
150 ON OFF
180 ON ON
35

Table of Contents

Other manuals for Carrier 58MTA

Related product manuals