UNIT DAMAGE HAZARD
Failure to follow this caution may result in premature failure
of the igniter.
The igniter is fragile. DO NOT allow it to hit burner box parts
while removing or replacing it.
e. If replacement is required, replace igniter on igniter bracket
and then install assembly into burner box to avoid damage
to the igniter.
6. To replace igniter and bracket assembly, reverse items 5a
through 5d.
7. Reconnect igniter wire connection and insert the igniter wires
in the slot in the manifold grommet, dressing the igniter wires
to ensure there is no tension on the igniter itself. (See Fig.7.)
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in electrical shock,
personal injury, or death.
Igniter wires must be securely placed in slot in manifold
grommet or else they could become pinched or severed and
electrically shorted.
8. Reinstall burner box cover.
9. Turn on gas and electrical supplies to furnace.
10. Verify igniter operation by initiating control board self-test
feature or by cycling thermostat.
11. Replace main furnace door.
Step 7—Electrical Controls and Wiring
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
There may be more than 1 electrical supply to the unit. Check
accessories and cooling unit for additional electrical supplies.
The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 15 for field wiring information
and to Fig. 21 for unit wiring information.
NOTE: If the polarity is not correct or furnace is not properly
grounded, the STATUS LED on the furnace control will flash
rapidly and prevent the furnace from operating. The control system
Fig. 11—Burner Flame
A89020
BURNER  FLAME
BURNER
MANIFOLD
Fig. 12—Gasket on Collector Box
A93081
RTV
PAM
→ Fig. 13—Igniter Bracket
A05075
BRACKET
IGNITER
9/16˝
11/16˝
EXTENDED IGNITER
BRACKET HANDLE
IGNITER BRACKET
MOUNTING SCREW
→ Fig. 14—Igniter
A04181
2-5/32˝
9
→
→
→
→
→