13
Electrical data
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
† Unit ampacity = 125% of largest operating component’s full load amps plus 100% of all other potential operating component’s (EAC, humidifier,
etc.) full load amps.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.
** Time-delay type is recommended.
Typical wiring schematic
UNIT SIZE 040-14 060-14 080-14 080-20 100-20 120-20
UNIT VOLTS — HERTZ — PHASE 115 — 60 — 1
OPERATING VOLTAGE RANGE (Min — Max)
* 104 — 127
MAXIMUM UNIT AMPS 8.9 8.9 8.9 13.8 13.8 11.6
UNIT AMPACITY† 12.0 12.0 12.0 17.9 18.1 15.3
MINIMUM WIRE SIZE 14 14 14 12 12 12
MAXIMUM WIRE LENGTH (Ft)‡ 31 31 31 32 32 37
MAXIMUM FUSE SIZE OR CKT BKR (Amps)
** 15 15 15 20 20 20
TRANSFORMER (24v) 40va
EXTERNAL CONTROL POWER AVAILABLE Heating 25va
Cooling 34va
AIR CONDITIONING BLOWER RELAY Standard
A98325
115-V
FIELD-SUPPLIED
DISCONNECT
SWITCH
115-V
SINGLE
PHASE
AUXILIARY
J-BOX
FURNACE
CONTROL
CENTER
TWO WIRE
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING
ONLY
FIVE
WIRE
NOTE 5
NOTE 1
NOTE
3
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
R
W2
WCR GY
GND
GND
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-, 208/230-, 460-V WIRING
208/230- OR
460-V
THREE PHASE
208/230-V
SINGLE
PHASE
W/W1
Y/Y2
G
C
NOTES:
1.
2.
3.
4.
5.
Connect Y or Y/Y2 terminal as shown for proper cooling operation.
Proper polarity must be maintained for 115-v wiring.
Use W2 with 2-stage thermostat when zoning.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
Some thermostats require a "C" terminal connection as shown.