Table 5—Electrical Data
UNIT SIZE
VOLTS—
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
MAX
UNIT
AMPS
MIN
WIRE
GAGE
MAX WIRE
LENGTH (FT)‡
MAX FUSE OR
CKT BKR AMPS†
Max* Min*
060-12 115—60—1 127 104 10.1 14 36 15
080-16 115—60—1 127 104 10.6 14 34 15
100-20 115—60—1 127 104 12.6 14 29 15
120-20 115—60—1 127 104 13.9 14 26 15
* Permissible limits of the voltage range at which the unit will operate satisfactorily.
Time-delay fuse is recommended.
Length shown is as measured along wire path between unit and service panel for maximum 2 percent voltage drop.
Fig. 13—Heating and Cooling Application Wiring Diagram:
1-Stage Thermostat and Single-Speed Condensing Unit
A99231
GREEN
DEHUM
115-V FIELD-
SUPPLIED
DISCONNECT
JUNCTION
BOX
CONTROL
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-
ONLY
FIVE
WIRE
NOTE 2
NOTE 1
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
CONDENSING
UNIT
FURNACE
NOTE 4
NOTE 5
Y1
AFS
COM
R
WCY RG
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
Y1 is not to be connected.
Connect O to thermostat-O only for heat pump applications.
Field-supplied humidistat for dehumidification in cooling (optional).
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
WHT
BLK
WHT
BLK
W/W1
W2
Y/Y2
G
NOTES: 1.
2.
3.
4.
5.
6.
O
NOTE 6
Fig. 14—Heating and Cooling Application Wiring Diagram:
2-Stage Thermostat and Two-Speed Condensing Unit
A99232
115-V FIELD-
SUPPLIED
DISCONNECT
JUNCTION
BOX
CONTROL
24-V
TERMINAL
BLOCK
FOUR-WIRE
HEATING-
ONLY
SEVEN
WIRE
2-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
2-SPEED
CONDENSING
UNIT
FURNACE
G
R
W2 Y2 G Y1
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
Y2
Y1
C
WHT
BLK
WHT
BLK
W1CR
W2
COM
W/W1
Y/Y2
Y1
AFS
NOTE 2
NOTE 1
Connect Y1 and Y/Y2 as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
Connect O to thermostat-O only for heat pump applications.
Field-supplied humidistat for dehumidification in cooling (optional).
NOTES: 1.
2.
3.
4.
5.
NOTE 4
O
NOTE 5
GREEN
DEHUM