5
NOT move or shuffle your feet, do not touch ungrounded
objects, etc.).
4. If you touch ungrounded objects (and recharge your body
with static electricity), firmly touch a clean, unpainted metal
surface of the furnace again before touching control or
wires.
5. Use this procedure for installed and uninstalled (ungroun-
ded) furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 4 before bringing the con-
trol or yourself in contact with the furnace. Put all used and
new controls into containers before touching ungrounded
objects.
7. An ESD service kit (available from commercial sources)
mayalsobeusedtopreventESDdamage.
ACCESSORIES
See Product Data Sheet for a list of accessories for this product.
Table 1 – Loose Parts Bag Contents (Provided in blower compartment)
Qty
Description
1 AirIntakePipeFlange
1 Vent Pipe Flange
2 Coupling Flange Gaskets
10 Sharp Tip Screws (Vent and Inlet Flanges)
1 Vent Pipe Coupling
2 Vent Pipe Coupling Clamps
1 Pressure Switch Tube
1 Outlet Choke Plate (used with 40k BTUH furnaces, only)
1 Drain Tube Elbow
1 Drain Extension Tube
2 Drain Tube Clamps
1 Drain Line Grommet
1 Gas Line Grommet
1 Gas Line Knockout Plug
1 Junction Box Cover
1 Junction Box Base
1 Green Ground Screw
3 Blunt Tip Screws (Junction Box)
1 Thermostat Wire Grommet
Table 2 – Minimum Clearances to Combustible Materials for All Units
POSITION CLEARANCE
REAR 0
FRONT (Combustion air openings in furnace and in structure) 1in.(25mm)
Required for service *24 in. (610 mm)
All Sides of Supply Plenum 1in.(25mm)
Sides 0
Vent 0
Top of Furnace 1in.(25mm)
*Recommended
59SP5A