4.9.17 - GENCONF menu
ramp_sel Yes/No No - Ramp loading sequence
o_on_d 1 to 15 1 min Start-up delay
nh_start 00:00 to 24:00 00:00 - Night mode start hour
nh_end 00:00 to 24:00 00:00 - Night mode stop hour
bas_menu 0 to 3 0 - Basic menu conguration
0 = total access
1 = access to the alarm menu by password
2 = access to the setpoint menu by password
3 = combination of 1 and 2
synoptic Yes/No No - Synoptic diagram display
4.9.18 - PUMPCONF menu
pump_seq Yes/No No - Heat exchanger pump availability
pump_per Yes/No No - Pump seizure protection
pump_sby Yes/No No - Pump shutdown when the unit is in standby
pump_loc Yes/No Yes - Flow rate verication when the pump has shut down
4.9.19 - HCCONFIG menu
hr_sel 0 to 3 0 - Heating reset selection
1 = outside temp., 0 = none, 2 = delta T
heat_th -20 to 0 -15 °C Outside temperature threshold heating mode
boil_th -30 to 15 -25 °C Outside temperature threshold for the boiler
ehs_th -5 to 21 5 °C Outside temperature threshold for electric heater stages
ehs_back Yes/No No - One backup electric heater stage
ehs_pull 0 to 60 0 minutes Delay before start-up of the rst electric heater stage
ehs_defr Yes/No No - Quick electric heat stages for defrost
4.9.20 - RESETCFG menu
oathr_non -10 to 51.7 -10 °C Outside temperature for no reset
oathr_fu -10 to 51.7 -10 °C Outside temperature for maximum reset
dt_hr_non -17.8 to -3.9 -17.8 ^C Delta T for no reset
dt_hr_fu -17.8 to -3.9 -17.8 ^C Delta T for maximum reset
v_hr_non -17.8 to -6.7 -17.8 ^C Current value for no reset
v_hr_fu -17.8 to -6.7 -17.8 ^C Current value for maximum reset
hr_deg -34.4 to 1.1 -17.8 ^C Heating mode reset value
4.9.21 - USERCONF menu
language 0 to 5 0 - Language selection
English = 0, Spanish = 1, French = 2, German = 3, Italian = 4,
Translation = 5
use_pass 1 to 9999 11 - User password
4.9.22 - DATETIME menu
hour 0 to 24 hours Hour
minutes 0 to 59 minutes Minutes
dow 1 to 7 - Day of the week
tom_hol No/Yes No - Holiday tomorrow?
tod_hol No/Yes No - Holiday today?
dlig_o No/Yes - Winter time change-over active?
dlig_on No/Yes - Summer time change-over active?
d_of_m 1 to 31 - Day of the month
month 1 to 12 - Month
year 0 to 99 - Year
4.9.23 - CTRL_ID menu
elemt_nb 1 to 239 1 - Element number
bus_nb 0 to 239 0 - Bus number
baudrate 9600 to 38400 9600 - Communication speed
61 AF Pro-Dialog+ Description
CSA-SR-20H430NN
-
Software version
Serial number