Application scheme
Unit description
See g. 1
Outdoor Unit1.
Hydronic module2.
Domestic hot water tank (optional)3.
Ball valves (eld supplied)4.
Water lter (eld supplied)5.
Collectors (eld supplied)6.
3 way valve (optional)7.
T1, T2, T3: terminals
C1, C2, C3: thermostats connected to terminals
C: user interface (additional or shifted from the unit) or
thermostat connected to hydronic module
Terminals
Terminals can be of the following types:
oor circuit•
fan coils•
radiators•
low temperature radiators•
Dierent terminals have dierent water temperature
requirements.
To ensure comfort, it is suggested not to use, at the
same time, terminals with dierent water temperature
requirements.
Example: it is possible to use oor circuit for heating and fan
coil for cooling, but using both at the same time (in heating
or cooling) will cause discomfort.
Floor circuit is the recommended terminal, as it ensures the
best energy eciency.
See g. 2
Outlet water pipe1.
Boiler pipes (only models 80AW----M0)2.
Inlet water pipe3.
Filling valve4.
Refrigerant pipes5.
See g. 3
User interface (mounted on unit)1.
Manometer2.
Water pump3.
Control box4.
Main board5.
See g. 4
Hydronic module1.
Wall bracket2.
Replacement cap for shifted user interface3.
Hydronic module manual4.
User interface manual5.
Terminal blok6.
Water temperature sensor - LWT7.
Expansion vessel8.
Flow switch9.
Pressure relief valve10.
Electric heater (not for models 80AW----M0)11.
Buer tank (10 lt)12.
Brazed plate heat exchanger13.
Water temperature sensor - TWB14.
Air purge valve15.
Refrigerant sensor - TC16.
Room temperature control
Dierent terminals (T1, T2…Tn) can be placed in a single
room or in multiple rooms.
Each of them can have a thermostat, to stop the terminal
when a certain temperature is reached.
It is possible to control 1 room with a user interface or a
thermostat connected to the unit.
This room should be the one with the highest heating/
cooling requirements.
In this room it is not required to place a thermostat on the
terminal/s.
It is suggested to place a thermostat on terminals placed in
rooms with signicantly dierent thermal requirements.
It is recommended to control the room with the user
interface; this way the control adjusts water temperature
to meet the setpoint and comfort and energy eciency are
optimized.
If no user interface is used:
if thermostats are used, set climatic curves slightly higher •
in heat mode and slightly lower in cool mode
if no thermostats are used (temperature requirements •
should be similar for all rooms), climatic curves must be
set exactly right for both heating and cooling operation