EasyManua.ls Logo

Carrier AIRSTREAM 42BHE - Unit Weights: 42 BHE Models

Carrier AIRSTREAM 42BHE
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
B
D
A
C
LEFT HAND UNIT
A
B
D
C
RIGHT HAND UNIT
42BHE UNIT CORNER WEIGHTS (lb)
CORNER WEIGHT
NOTE: Unit weights (shown in pounds) ±10%, are based on the 8-row water filled coils, double
wall cabinet construction, and 1 hp motor.
UNIT
42BHE
NO ELECTRIC HEAT (lb)
TOTAL
WEIGHT
WITH ELECTRIC HEAT (lb)
TOTAL
WEIGHT
ABCD ABCD
06 58 63 55 59 235 58 66 67 75 266
08 59 67 67 76 269 58 67 67 76 268
10 73 81 65 73 292 72 86 78 91 327
12 74 82 66 74 296 73 86 78 92 329
16 92 99 81 88 360 91 103 94 107 395
20 105 113 89 97 404 105 117 103 115 440
30 135 144 109 117 505 135 148 123 136 542
40 176 183 135 143 637 176 187 150 161 674
TOTAL WEIGHT UNIT CORRECTION FACTOR (lb)
NOTE: Corner weights are for 8-row water filled coils. For a different number of rows, total unit weight can be
determined by the following procedure:
1. Identify the number of rows, the size of the unit, and cabinet construction.
2. Determine the total weight of the unit from the Corner Weight table above.
3. From the table above, identify the correction factors and deduct this from the total weight.
4. Motor, coil stub out, and control box are always located on same side of the unit.
UNITS
42BHE
4 ROWS 5 ROWS 6 ROWS 7 ROWS
SINGLE WALL
CONSTRUCTION
Correction Factors (lb)
06 -21 -16 -11 -5 -31
08 -21 -16 -11 -5 -31
10 -28 -21 -14 -7 -40
12 -28 -21 -14 -7 -40
16 -39 -29 -20 -10 -47
20 -46 -35 -23 -12 -58
30 -74 -55 -37 -18 -67
40 -98 -74 -49 -25 -82
a42-4245
Base unit dimensions (cont)