EasyManua.ls Logo

Carrier AIRSTREAM 42BHE - Electrical Data and Motor Performance; Electric Heater Data Availability; Motor Performance Data

Carrier AIRSTREAM 42BHE
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
42BHE,BVE ELECTRIC HEATER DATA AVAILABILITY 42BHE,BVE ELECTRIC HEATER DATA
LEGEND
NOTES:
1. Stages available:
a. Single phase: 1 to 12 kW, 1 stage only
3 to 12 kW, 1 stage or 2 stage
b. Three phase: 1 to 39.9 kW, 1 stage only
4 to 39.9 kW, 1 or 2 stage
12 to 39.9 kW, 1, 2 or 3 stage
2. Electric Heating Capacities (Btuh) = Heater kW x 3413
3. Electric Heater Amperage for Single-phase Power = (Heater kW x 1000)/Applied Voltage
Electric Heater Amp. for 3-phase Power = (Heater kW x 1000)/(Applied Voltage x 1.73).
MOTOR PERFORMANCE DATA (FULL LOAD AMPS)
NOTES:
1. Motor full load amps refer to National Electric Code (NEC) amps;
actual motor nameplate amps may vary.
2. NEC data extrapolated for 277 v.
3. Motors are open drip proof, ball bearing, single speed, 1750 rpm
rated at continuous duty, 104 F ambient with reversible rotation.
4. 5 hp motors available only on size 40 units.
Service switches:
The service switch is an On/Off switch on incoming power
supply to unit. Proper amperage load must be determined
before switch can be selected. The range of the fused or
non-fused service switch is 0 to 40 amps.
MCA (minimum circuit amps) = 1.25 x sum of all
loads.
MFS (maximum fuse size) = MCA rounded up to next
available fuse size.
kW
42BHE UNIT SIZE
06 08 10 12 16 20 3040
1.0 ●●——————
1.5 ●●●●————
2.0 ●●●●————
2.5 ●●●●●———
3.0 ●●●●●———
3.5 ●●●●●●——
4.0 ●●●●●●——
4.5 ●●●●●●——
5.0 ●●●●●●——
6.0 ●●●●●●●●
7.0 ●●●●●●●
8.0 ●●●●●●●
9.9 ——●●●●●●
12.0 ——●●●●
14.0 ————●●●●
15.0 ————●●●●
16.0 ————●●●●
18.0 —————●●●
19.9 —————●●●
25.0 ——————●●
30.0 ——————●●
35.0 ———————
39.9 ———————
kW
FULL LOAD AMPS
Single-Phase Three-Phase
115 V 208 V 240 V 277 V 208 V240 V480 V
1.0 8.3 4.8 4.2 3.6 2.8 2.4 1.2
1.5 12.5 7.2 6.3 5.4 4.2 3.6 1.8
2.0 16.7 9.6 8.3 7.2 5.6 4.8 2.4
2.5 20.8 12.0 10.4 9.0 6.9 6.0 3.0
3.0 25.0 14.4 12.5 10.8 8.3 7.2 3.6
3.5 29.2 16.8 14.6 12.6 9.7 8.4 4.2
4.0 33.3 19.2 16.7 14.4 11.1 9.6 4.8
4.5 37.5 21.6 18.8 16.2 12.5 10.8 5.4
5.0 24.0 20.8 18.1 13.9 12.0 6.0
6.0 28.8 25.0 21.7 16.7 14.4 7.2
7.0 33.7 29.2 25.3 19.4 16.8 8.4
8.0 38.5 33.3 28.9 22.2 19.2 9.6
9.9 35.7 27.5 23.8 11.9
12.0 43.3 33.3 28.9 14.4
14.0 ————38.933.716.8
15.0 ————41.636.118.0
16.0 —————38.519.2
18.0 ——————21.7
19.9 ——————23.9
25.0 ——————30.1
30.0 ——————36.1
35.0 ——————42.1
39.9 ——————48.0
Standard Offering
Not Offered
VOLTAGE
V-Ph-Hz
Nominal HP
1
/
4
1
/
3
1
/
2
3
/
4
11
1
/
2
2 3 5
115-1-60 5.2 6.0 8.6 13.3 14.4
208-1-60 3.0 3.6 4.8 6.6 7.4 9.4 11.0
230-1-60 2.5 3.0 4.2 5.1 6.0 9.0 10.9
277-1-60 2.1 2.5 3.6 5.1 5.4 8.5 8.0
208-3-60 2.4 3.6 3.8 6.0 6.5 8.2 14.0
230-3-60 2.2 3.0 3.2 4.8 6.2 8.0 13.2
460-3-60 1.1 1.5 1.9 2.8 3.1 4.0 6.6