Table 14 — Option Configuration
Main Menu
Configuration MenuOption Configuration [CONF_OPT]
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option
Dsable/Enable - Dsable Jobsite specific
Common Sensor Option
Dsable/Enable - Dsable Jobsite specific
EC Valve Option
No=0, Cont.=1,ON/OFF=2, mA=3
0 to 3 - 0 2 (if selected)
EC Selection
Disable=0, Surge=1, Low Load=2,
Comb=3
0 to 3 - 0 Jobsite specific
ECV Open IGV1 Position
0.5 to 10.0 % 5 5 (adjust as required)
ECV Close IGV1 Position
1.5 to 20.0 % 10 10 (adjust as required)
ECV Off DT for Low Load
0.5 to 10 ^F 4 4 (adjust as required)
ECV On DT for Low Load
0.5 to 10 ^F 2 2 (adjust as required)
ECV Low Load DB
0.5 to 2.0 ^F 1 1 (adjust as required)
Head Pres Valve Option
Dsable/Enable - Dsable Jobsite specific
Head Pres Delta P 0%
20 to 85 PSI 25 25 (adjust as required)
Head Pres Delta P 100%
20 to 85 PSI 50 50 (adjust as required)
Head Pressure Min Output
0 to 100 % 0 0 (adjust as required)
Tower Fan High Setpoint
55 to 105 °F 75 75 (adjust as required)
Refrig Leakage Option
Dsable/Enable - Dsable Jobsite specific
Refrig Leakage Alarm mA
4 to 20 mA 20 20 (adjust as required)
Oil EXV Option
Dsable/Enable - Dsable Dsable
Oil Temp High Threshold
100 to 140 °F 122 n/a
Oil Temp Low Threshold
90 to 130 °F 113 n/a
Gas Torque Factor
0.25 to 3.00 - 1 1
Guide Vane/SRD Factor
0.70 to 1.20 - 0.95 0.95
Power Recovery Timeout
0 to 60 min 15 15
Condenser Flush Alert
Dsable/Enable - Dsable Dsable
Customer Alert Option
Dsable/Enable - Dsable Jobsite specific
Ice Build Option
Dsable/Enable - Dsable Jobsite specific
Ice Build Recycle
Dsable/Enable - Dsable Jobsite specific
Ice Build Termin Source
Temp=0,Contact=1,Both=2
0 to 2 - 0 Jobsite specific
Water Pressure Option
No=0, Pres.=1, Pres.D=2
0 to 2 - 0 Jobsite specific
Water Flow Measurement
No=0, Flow Meter=1,Water Pres.
D=2
0 to 2 - 0 Jobsite specific
Water Flow Determination
Sat Temp=0,Flow Switch=1
0 to 1 - 0 Jobsite specific
Water Flow at 4mA
0 to 200 GPS 0 (adjust as required)
Water Flow at 20mA
0 to 200 GPS 0 (adjust as required)
Evap Flow Rate Baseline
0 to 150 GPS 0 (adjust as required)
Evap Pres Drop Baseline
0 to 20 PSI 0 (adjust as required)
Cond Flow Rate Baseline
0 to 150 GPS 0 (adjust as required)
Cond Pres Drop Baseline
0 to 20 PSI 0 (adjust as required)
Water Pres Drop @20mA
10 to 40 PSI 10 (adjust as required)
Max Oil Pressure Diff
35 to 60 PSI 50 n/a
Oil Pump VFD Max Step
0 to 10 % 7 n/a
Vapor Source SV Delay
0 to 10 min 5 n.a
Vapor Source SV Option
Dsable/Engale - Dsable n.a
Liquid Bypass Selection
Dsable/Enable - Dsable Per selection
Purge On Idle Option
Dsable/Enable - Dsable
(adjust as required for
force)
Evap Liquid Temp Opt
Dsable/Enable - Enable n/a
Evap App Calc Selection
Sat Temp=0, Ref Temp=1
0 to 1 - 1 1