31
Table 15 — Service Parameters Table
Menu
Configuration MenuService Parameters [SERVICE]
*Most Service Parameters do not require any change from default.
Adjust as required.
Field Set Up and Verification
Use the HMI touch screen to confirm that the VFD values
match the chiller parameter labels and Chiller Builder design
data sheet. The VFD values can be located from MAIN
MENU CONFIGURATION MENU.
LABEL LOCATIONS — Verify the following labels have
been installed properly and match the chiller requisition:
• Surge Parameters — Located inside the HMI chiller con-
trol panel.
• Chiller identification nameplate — Located on the left
side of the control panel. (See Fig. 28.)
• VFD Nameplate data - located on the right side of the VFD.
MODIFY EQUIPMENT CONFIGURATION IF NECES-
SARY — The EQUIPMENT SERVICE table has screens to
select, view, or modify parameters. Carrier’s certified drawings
have the configuration values required for the jobsite. Modify
these values only if requested. Modifications can include:
• Chilled water reset
• Entering chilled water control (Enable/Disable)
• 4 to 20 mA demand limit
• Auto restart option (Enable/Disable)
• Remote contact option (Enable/Disable)
See the 19DV with PIC5 Controls Operation and Trouble-
shooting guide for more details about these functions; see the
Control Panel Schematic for field wiring.
Fig. 28 — Machine Identification Nameplate and
VFD Electrical Nameplate
Perform a Controls Test (Quick Calibration/
Quick Test) —
Check the safety controls status by per-
forming an automated controls test. First, perform a Quick Cali-
bration Test (Path Main Menu→ Quick Calibration. This is
DESCRIPTION MENU NAME RANGE DEFAULT UNITS VALUE*
Service Password ser_pass 0 to 65535 2222 -
Atmospheric Pressure atom_pre 8 to 15 14.5 PSI
GV1 Travel Limit gv1_lim 30 to 100 80.7 %
GV1 Closure at Startup gv1stpos 0 to 40 4 %
Controlled Fluid DB ctrl_db 0.5 to 2 1 ^F
Derivative EWT Gain ewtdgain 1 to 3 2 -
Proportional Dec Band gv1decdb 2 to 10 6 -
Proportional Inc Band gv1incdb 2 to 10 6.5 -
Maximum GV Movement max_gv 1.0 to 4.0 2 %
Demand Limit At 20 mA dem_20ma 10 to 100 40 %
Demand Limit Prop Band dem_pdb 3 to 15 10 %
Amps or KW Ramp per Min ldramprt 5 to 20 5 %
Temp Ramp per Min tmramprt 1 to 10 3 ^F
Recycle Shutdown Delta T rcysh_dt 0.5 to 4 1 ^F
Recycle Restart Delta T rcyst_dt 2 to 10 5 ^F
Damper Valve Act Delay dmp_dly 1 to 5 2 min
Damper Valve Close DB dmp_cldb 2 to 10 5 PSI
Damper Valve Open DB dmp_opdb 10 to 20 13 PSI
Damper Action Delta T dmp_dt 4 to 10 7 ^F
Lub Press Verify Time oilpvr_t 15 to 300 40 sec
Soft Stop Amps Threshold sf_st_th 40 to 100 70 %
Water Flow Verify Time wflow_t 0.5 to 5 5 min
Power Calibration Factor mbb_pfcl 0.5 to 2 1 -
Enable Excessive Starts ex_start No/Yes No -
Purge Active Temp SP pgt_set 30 to 90 65 -
Oil Stir Cycle(19XR6/7)
No Stir=0, 30s/30m=1,
1m/4h=2, Comb. 0&1=3
oilstiro 0 to 3 1 -
IMPORTANT: Some parameters are specific to the chiller
configuration and will need to be verified prior to operation.
All command functions must be initiated from the HMI.