EasyManuals Logo

Carrier AquaEdge 19DV series User Manual

Carrier AquaEdge 19DV series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
7
REFRIGERATION CYCLE
The compressor continuously draws refrigerant vapor from
the evaporator at a rate set by the amount of first stage guide
vane opening and motor speed. As the compressor suction re-
duces the pressure in the evaporator, the remaining refrigerant
boils at a fairly low temperature (typically 38 to 42°F [3 to
6°C]). The energy required for boiling is obtained from the wa-
ter flowing through the evaporator tubes. With heat energy re-
moved, the water becomes cold enough to use in an air-condi-
tioning circuit or process liquid cooling.
After taking heat from the water, the refrigerant vapor is com-
pressed by a back-to-back compression connected by means of
interstage piping. Compression adds heat energy and the refrig-
erant is quite warm (typically 98 to 102°F [37 to 40°C]) when it
is discharged from the compressor into the condenser.
Relatively cool (typically 65 to 90°F [18 to 32°C]) water
flowing into the condenser tubes removes heat from the refrig-
erant, and the vapor condenses to liquid. The liquid drains into
a high side float valve chamber between the condenser and the
economizer. The refrigerant is then metered into the economiz-
er. In the economizer, due to lower pressure, as liquid enters the
chamber, some liquid will flash into a vapor and cool the re-
maining liquid. The separated vapor flows to the second stage
of the compressor for greater cycle efficiency. The second
stage guide vane on the compressor acts as a pressure regulat-
ing device to stabilize operating conditions. At part load the
second stage guide vane will back up gas flow and thereby rais-
es the economizer pressure to allow appropriate refrigerant
flow from economizer to the compressor.
The cooled liquid left in the economizer flows through a
low side float valve and then into the evaporator. The float
valve forms a liquid seal to keep vapor from entering the
evaporator. The refrigerant is now at a temperature and
pressure at which the cycle began. Fig. 3 summarizes the re-
frigeration cycle.
The 19DV unit utilizes R-1233zd(E) refrigerant. At at-
mospheric pressure its boiling point is 65.5°F (18.6°C).
The result is that at normal operating conditions the evapo-
rator typically will be in a vacuum condition and the con-
denser will operate at a pressure above atmospheric pres-
sure. Unit near room temperature will be close to atmo-
spheric pressure.
Fig. 3 — Refrigeration Cycle — 19DV Two-Stage Compressor
HIGH SIDE FLOAT
CHAMBER
COOLER
ECONOMIZER
LOW SIDE
FLOAT CHAMBER
CONDENSER
COMPRESSOR

Table of Contents

Other manuals for Carrier AquaEdge 19DV series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier AquaEdge 19DV series and is the answer not in the manual?

Carrier AquaEdge 19DV series Specifications

General IconGeneral
BrandCarrier
ModelAquaEdge 19DV series
CategoryChiller
LanguageEnglish

Related product manuals