EasyManua.ls Logo

Carrier AquaEdge 19XR series - MOTOR AND OIL COOLING CYCLE

Carrier AquaEdge 19XR series
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
MOTOR AND OIL COOLING CYCLE
The motor and the lubricating oil are cooled by liquid refriger-
ant taken from the bottom of the condenser vessel (Fig. 4 and
5). Refrigerant flow is maintained by the pressure differential
that exists due to compressor operation. After the refrigerant
flows past an isolation valve, an in-line filter, and a sight glass/
moisture indicator, the flow is split between the motor cooling
and oil cooling systems.
Fig. 5 — Refrigeration Cycle — 19XR,XRV Two-Stage Compressor
IMPORTANT: To avoid adverse effects on chiller opera-
tion, considerations must be made to condenser water tem-
perature control. For steady state operation, the minimum
operating refrigerant pressure differential between cooler
and condenser is approximately 20 psi (138 kPa) with a
maximum evaporator refrigerant temperature of 65 F
(18 C). Consult Chiller Builder for required steady state
operational limits. Inverted start conditions are acceptable
for short durations of time, but for periods exceeding 5
minutes, a special control solution strategy should be used
to allow the chiller to establish a minimum refrigerant pres-
sure differential (and thereby adequate equipment cooling).

Table of Contents

Other manuals for Carrier AquaEdge 19XR series

Related product manuals