EasyManua.ls Logo

Carrier AquaEdge 19XR series - TIME SCHEDULE OPERATION (Fig. 22)

Carrier AquaEdge 19XR series
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
To Remove a Force
1. On the point status table press or
to highlight the desired value.
2. Press to access the highlighted value.
3. Press to remove the override and return the
point to the PIC II’s automatic control.
Force Indication
— A forced value is indicated by
“SUPVSR,” “SERVC,” or “BEST” flashing next to the point
value on the STATUS table.
TIME SCHEDULE OPERATION (Fig. 22)
On the Menu screen, press .
4. Press or to highlight the desired
schedule.
OCCPC01S — LOCAL Time Schedule
OCCPC02S — ICE BUILD Time Schedule
OCCPC03S — CCN Time Schedule
5. Press to view the desired time schedule.
6. Press or to highlight the desired
period or override to change.
7. Press to access the highlighted period or over-
ride.
8. a. Press or to change the
time values. Override values are in one-hour
increments, up to 4 hours.
b. Press to select days in the day-of-week
fields. Press to eliminate days from the
period.
9. Press to register the values and to move horizon-
tally (left to right) within a period.
10. Press to leave the period or override.
11. Either return to Step 4 to select another period or over-
ride, or press again to leave the current time sched-
ule screen and save the changes.
12. The Holiday Designation (HOLIDEF table) may be
found in the Service Operation section, page 63. The
month, day, and duration for the holiday must be
assigned. The Broadcast function in the BRODEF
table also must be enabled for holiday periods to
function.
NEXT
PREVIOUS
SELECT
RELEASE
SCHEDULE
NEXT
PREVIOUS
SELECT
NEXT
PREVIOUS
SELECT
Fig. 22 — Example of Time Schedule
Operation Screen
INCREASE
DECREASE
ENABLE
DISABLE
ENTER
EXIT
EXIT