APPENDIX D — BACNET COMMUNICATION OPTION (cont)
Table G — UPC Open Points List for Version 14 19XR Software
LEGEND
POINT DESCRIPTION
CCN
POINT NAME
READ/
WRITE
UNITS RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Active Demand Limit DEM_LIM R/W % 40 to 100 AV:6 dem_lim_1
Actual Guide Vane Position GV_POS R % AV:7 gv_pos_1
Actual Line Current AMPS_A R A AV:8 amps_a_1
Actual Line Voltage VOLT_A R V AV:9 volt_a_1
Actual VFD Speed VFD_ACT R % AV:11 vfd_act_1
Calc Evap Sat Temp ERT R °F AV:13 ert_1
Chilled Water Deadband CWDB R ^F AV:14 cwdb_1
Chilled Water Delta P CHWPD R ^F AV:15 chwpd_1
Chilled Water Delta T CHW_DT R ^F AV:16 chw_dt_1
Chilled Water Pump CHWP R BV:4 chwp_1
Chilled Water Temp CHW_TMP R °F AV:17 chw_tmp_1
Chiller S/S CHIL_S_S R/W STOP/START BV:5 chil_s_s_1
Comp Discharge Temp CMPD R °F AV:18 cmpd_1
Comp Motor Winding Temp MTRW R °F AV:19 mtrw_1
Comp Thrust Brg Temp MTRB R °F AV:20 mtrb_1
Condenser Pressure CRP R PSI AV:21 crp_1
Condenser Refrig Temp CRT R °F AV:22 crt_1
Condenser Water Delta P CDWPD R PSI AV:23 cdwpd_1
Control Point LCW_STPT R/W °F -10 to 120 AV:24 lcw_stpt_1
Cond Water Flow CDW_FLOW R BV:6 cdw_flow_1
Cond Water Pump CDP R BV:7 cdp_1
Current CHW Setpoint CHWSTPT R °F AV:25 chwstpt_1
Demand Level 1 N/A R % AV:1
dmv_lvl_1_perct_
1
Demand Level 2 N/A R % AV:2
dmv_lvl_2_perct_
1
Demand Level 3 N/A R % AV:3
dmv_lvl_3_perct_
1
Element Communications Alarm N/A R BV:20
com-
m_lost_alm_1
Element Comm Status N/A R BV:2999 element_stat_1
Emergency Stop EMSTOP R BV:8 emstop_1
Entering Chilled Water ECW R °F AV:26 ecw_1
Entering Condenser Water ECDW R °F AV:27 ecdw_1
Equipment Alarm N/A R BV:21 element_alarm_1
Evaporator Pressure ERP R PSI AV:28 erp_1
Frequency FREQ R Hz AV:30 freq_1
Hardware Failure HARDWARE R BV:9 hardware_1
Leaving Chilled Water - Prime
Variable
LCW R °F AV:31 lcw_1
Leaving Condenser Water LCDW R °F AV:32 lcdw_1
Local Schedule N/A R BV:2 schedule_1
Occupied? OCC R BV:10 occ_1
Oil Sump Temperature OILT R °F AV:33 oilt_1
Overload Trip OVERLOAD R BV:12 overload_1
Power Factor
POW_FACT R AV:34 pow_fact_1
Remote Start Contact REMCON R/W OPEN/CLOSE BV:11 remcon_1
Run Status STATUS R
0=Timeout
1=Ready
2=Recyle
3=Startup
4=Running
5=Demand
6=Ramping
7=not used
8=Override
9=Tripout
10=Control
AV:35 status_1
Service Ontime S_HRS R/W hr 0 to 32767 AV:36 s_hrs_1
CHW Chilled Water
R—Read
VFD Variable Frequency Drive
W—Write