CL-6
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option 0/1 DSABLE/ENABLE DSABLE
Guide Vane Closure 4 to 25 % 4
Remote Contacts Option 0/1 DSABLE/ENABLE DSABLE
Soft Stop Amps Threshold 40 to 100 % 100
Surge / Hot Gas Bypass
Surge Limit/HGBP Option 0, 1, 2 0
Select: Surge=0, HGBP=1
Low Load HGBP=2
Minimum Load Point
Surge/HGBP Delta Tsmin 0.0 to 150.0 ˆF 45
Surge/HGBP IGVmin 0.0 to 110.0 % 5.0
Full Load Point
Surge/HGBP Delta Tsmax 0.0 to 150.0 ˆF 70
Surge/HGBP IGVmax 0.0 to 110.0 % 5.0
Surge Line Shape Factor –1.000 to 0.000 –0.040
Surge Line Speed Factor 0.00 to 3.00 1.85
Surge Line High Offset 0.1 to 3.0 1.0
Surge/HGBP Deadband 0.5 to 3 ˆF 1
HGBP On Delta T 0.5 to 10.0 ˆF 2.0
HGBP Off Delta T 0.5 to 10.0 ˆF 4.0
Surge Protection
Surge Delta% Amps 5 to 40 % 20
Surge Time Period 7 to 10 MIN 8
Surge Delay Time 0 to 120 SEC 0
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE DSABLE
Ice Build Termination 0 to 2 0
0=Temp, 1=Contact, 2=Both
Ice Build Recycle 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Alarm mA 4 to 20 mA 20
Head Pressure Reference
Delta P at 0% (4mA) 20 to 85 PSI 25
Delta P at 100% (20mA) 20 to 85 PSI 50
Minimum Output 0 to 100 % 0