CL-5
19XR PIC 6 ISM CONFIGURATION TABLE (CONF_ISM) CONFIGURATION SHEET
(Must be configured for all fixed speed machines with ISM, Benshaw MX3, freestanding VFD)
19XR PIC 6 General VFD Config (CFGGEVFD) CONFIGURATION SHEET
(Must be configured for all machines with VFD
UM VFD Configuration
DESCRIPTION RANGE UNITS DEFAULT VALUE
Communication Timeout 0 to 255 sec 10
Starter Type
0 = Full Volt 1 = Reduced Volt
2 = Solid State 3 = FS VFD
0 to 3 0
Single Cycle Dropout DSABLE/ENABLE DSABLE
Motor Rated Load Amps 10 to 5000 amps 200
Motor Rated Kilowatts 1000 to 8000 kW 1500
Motor Locked Rotor Trip 100 to 65535 amps 1000
Locked Rotor Start Delay 1 to 10 cycles 5
Starter LRA Rating 100 to 65535 amps 2000
Motor Rated Line Voltage 200 to 13800 volts 460
Current Imbal Threshold 5 to 100 % 15
Voltage Imbal Threshold 1 to 10 % 5
Motor Current CT Ratio:1 3 to 1000 100
Volt Transformer Ratio:1 1 to 115 1
Current Imbal Persist 1 to 10 sec 5
Voltage Imbal Persist 1 to 10 sec 5
Line Frequency Faulting DSABLE/ENABLE DSABLE
Frequency (NO = 50 Hz, YES = 60 Hz) NO/YES NO
Ground Fault Protection DSABLE/ENABLE ENABLE
Ground Fault Current 1 to 25 amps 15
Ground Fault Persistence 1 to 10 cycles 5
Ground Fault Start Delay 1 to 20 cycles 10
Ground Fault CT Ratio:1 150 to 150 150
Overvoltage Threshold 105 to 115 % 115
Undervoltage Threshold 85 to 95 % 85
Over Under Volt Persist 1 to 10 sec 5
Under Volt Start Delay 1 to 4 sec 1
DESCRIPTION RANGE UNITS DEFAULT VALUE
VFD Current Limit 0 to 99999 amps 250
DESCRIPTION RANGE UNITS DEFAULT VALUE
Compressor Speed 100% 47
to 110 Hz 50
Rated Line Voltage 200-13800 V 460
Motor Nameplate Current 10 to 2000 AMPS 200
Motor Rated Load Current 10 to 2000 AMPS 200
Motor Nameplate Voltage 200 to 13800 Volts 460
Motor Nameplate RPM 1500 to 3600 rpm 3000
Motor Nameplate KW 0 to 5600 KW 1500
Skip Frequency 1 0.0 to 102.0 Hz 102
Skip Frequency 2 0.0 to 102.0 Hz 102
Skip Frequency 3 0.0 to 102.0 Hz 102
Skip Frequency Band 0.0 to 102.0 Hz 0
Motor Rated Load Current 10 to 1500 AMPS 200
Increase Ramp Time 5 to 60 sec 30
Decrease Ramp Time 5 to 60 sec 30
Line Voltage Imbalance% 1 to 10 % 10
Line Volt Imbalance Time 1 to 10 sec 10
Line Current Imbalance% 5 to 40 % 40
Line Current Imbal Time 1 to 10 sec 10
Motor Current Imbalance% 5 to 40 % 40
Motor Current Imbal Time 1 to 10 sec 10
Single Cycle Dropout 0 to 1 0
PWM Switch Frequency
0=2KHZ, 1=4KHZ
0 to 1 0