CL-6
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
19XR PIC 6 OPTION CONFIGURATION TABLE (CONF_OPT) CONFIGURATION SHEET
19XR PIC 6 OPTION CONFIGURATION TABLE (CONFOPT2) CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
CONF_OPT DSABLE/ENABLE ENABLE
Auto Restart DSABLE/ENABLE DSABLE
Swift Restart Option DSABLE/ENABLE ENABLE
Gas Torque Factor 0.25 to 3 1.00
Guide Vane/SRD Factor 0.7 to 1.2 0.95
Power Recovery Timeout 0 to 60 min 15.0
Common Sensor Option DSABLE/ENABLE DSABLE
EC/HC Valve Option
0=No, 1=Cont., 2=On/Off, 3=mA
0
EC/HC Valve Selection
0=Disable, 1=Surge,
2=Low Load, 3=Comb
0
EC/HG VLV Open IGV1 Pos 5 to 10 % 5
EC/HG VLV Close IGV1 Pos 1.5 to 35 % 10
EC/HG VLV Low Load DB 0.5 to 2 ^F 1.0
HPR VLV Option DSABLE/ENABLE DSABLE
HPR VLV Delta Pos 0% 0 to 85 PSI 25
HPR VLV Delta Pos 100% 0 to 85 PSI 50
HPR VLV Min Output 0 to 100 % 0.0
HPR VLV Deadband 0 to 10 1.0
Tower Fan High Setpoint 55 to 105 °F 75
Refrig Leakage Option DSABLE/ENABLE DSABLE
Refrig Leakage Alarm mA 4 to 20 mA 20
Oil Cooler EXV Option DSABLE/ENABLE DSABLE
Oil Temp High Threshold 100 to 140 °F 122
Oil Temp Low Threshold 90 to 130 °F 113
Customer Alert Option DSABLE/ENABLE DSABLE
Ice Build Option DSABLE/ENABLE DSABLE
Ice Build Recycle DSABLE/ENABLE DSABLE
Ice Build Termin Source
0=Temp, 1=Contact, 2=Both
0
Vapor Source SV Option DSABLE/ENABLE DSABLE
Vapor Source SV Delay 0 to10 min 5
Evap Liquid Temp Opt DSABLE/ENABLE ENABLE
Evap App Calc Selection
0=Sat Temp, 1=Ref Temp
1
DESCRIPTION RANGE UNITS DEFAULT VALUE
IOB3 Option No/Yes No
IOB4 Option No/Yes No
Water Pressure Option
0=No
1=WTR Flow PD TRD
(pressure transducers)
2=WTR Flow PD TRM
(4-20 mA differential water flow
pressure transmitter)
0
Water Flow Measurement
0=No
1=WTR Flow MTR
(4-20 mA water flow sensors)
2=WTR Flow PD
(based on water pressure drop
measurement
0
Free Cooling Option No/Yes No
Water Flow Determination
0=Sat Temp, 1=Flow Switch,
2=WTR Flow PD
Marine Option Disable/Enable Disable