CL-7
19XR PIC 6 SRD TABLE CONFIGURATION SHEET
19XR PIC 6 PROTECTIVE LIMIT TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Diffuser Option DSABLE/ENABLE DSABLE
SRD IGV Offset Select 1 to 5 3
Low Lift Profile Select 1 to 5 3
Diffuser Full Span mA 15.0 to 22.0 mA 18.0
GV 1 Pos @ 25% Load 0.0 to 83.0 % 6.4
GV 1 Pos @ 50% Load 0.0 to 83.0 % 22.9
GV 1 Pos @ 75% Load 0.0 to 83.0 % 41.3
SRD POS @ 25% Load 0.0 to 100.0 % 73.5
SRD POS @ 50% Load 0.0 to 100.0 % 35.1
SRD POS @ 75% Load 0.0 to 100.0 % 19.5
High Lift @ 100% Load 0.0 to 100.0 ^F 67.5
High Lift @ 25% Load 0.0 to 100.0 ^F 52.4
Low Lift @ 25% Load 0.0 to 100.0 ^F 27.2
Peak Detection Threshold 0.0000 to 5.0000 Volts 0.0000
DESCRIPTION RANGE UNITS DEFAULT VALUE
Evap Approach Alert 0.5 to 15.0 ^F 5.0
Cond Approach Alert 0.5 to 15.0 ^F 6.0
Cond Press Override Low 90.0 to 157.0 psi 140.0
Cond Press Override High 200.0 to 265.0 psi 250.0
Cond Press Cutout Low 160.0 to 165.0 °F 160.0
Cond Press Cutout High 270.0 to 275.0 °F 275.0
Evap Override Delta T 2.0 to 5.0 ^F 3.0
Evap Refrig Trippoint 0.0 to 40.0 °F 33.0
High Evap Press Override 90 to 157 psig 140
High Evap Press Cutout 160 to 170 °F 165
Condenser Freeze Point –20.0 to 35.0 °F 34.0
Comp Discharge Alert 125.0 to 200.0 °F 200.0
Comp Motor Temp Override 150.0 to 200.0 °F 200.0
Comp Bearing Temp Alert 155.0 to 175.0 °F 175.0
Comp Bearing Temp Trip 175.0 to 185.0 °F 185.0
Comp Bearing Alert XR6/7 185.0 to 210.0 °F 210.0
Comp Bearing Trip XR6/7 210.0 to 220.0 °F 220.0
Minimum Brine LWT 10.0 to 34.0 °F 34.0
Heating LWT Protect Set 41.0 to 50.0 °F 42.8
Evap Flow Delta P Cutout 0.5 to 50.0 psi 5.0
Cond Flow Delta P Cutout 0.5 to 50.0 psi 5.0
Cond Hi Flow DP Limit 0.5 to 50.0 psi 50.0
Cond Hi Flow Alarm DSABLE/ENABLE DSABLE