19XR PIC 6 SERVICE PARAMETERS TABLE CONFIGURATION SHEET
19XR PIC 6 GEN_CONF TABLE CONFIGURATION SHEET
19XR PIC 6 RESETCFG TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Atmospheric Pressure 8 to 15 psi 14.5
GV1 Travel Limit 30 to 100 % 80
GV1 Closure at Startup 0 to 40 % 4
Controlled Fluid DB 0.5 to 2.0 ^F 1
Derivative EWT Gain 1.0 to 3.0 2.0
Proportional Dec Band 2.0 to 10.0 6
Proportional Inc Band 2.0 to 10.0 6.5
Maximum GV Movement 2 to 4 % 2
Demand Limit At 20 mA 10 to 100 % 40
Demand Limit Prop Band 3.0 to 15.0 % 10.0
Amps or KW Ramp per Min. 5.0 to 20.0 10.0
Temp Ramp Rate per Min. 1 to 10 ^F 3
Recycle Shutdown Delta T 0.5 to 4.0 °F 1
Recycle Restart Delta T 2.0 to 10.0 °F 5.0
Damper Valve Act Delay 0 to 20 min 5
Damper Valve Close DB 2.0 to 10.0 ^psi 5.0
Damper Valve Open DB 10.0 to 20.0 ^psi 13.0
Damper Action Delta T 4.0 to 10.0 ^F 7.0
Oil Press Verify Time 15 to 300 sec 40
Soft Stop Amps Threshold 40 to 100 % 70
Water Flow Verify Time 0.5 to 5.0 min 5.0
Power Calibration Factor 0.900 to 1.000 0.97
Enable Excessive Starts NO/YES NO
Oil Stir Cycle (19XR6/7)
0 = No stir, 1 = 30s/30m
2 = 1m/4hr, 3 = Comb 0&1
0 to 3 1
DESCRIPTION RANGE UNITS DEFAULT VALUE
Stop to Start Delay 1 to 15 min 2
Start to Start Delay 4 to 45 min 15
Demand Limit Type
0 = Base Demand
1 = 4 to 20 mA
0 to 1 0
Pulldown Ramp Type
0 = Temp
1 = Load
0 to 1 1
Demand Limit Source
0 = Amps
1 = KW
0 to 1 0
DESCRIPTION RANGE UNITS DEFAULT VALUE
Temp Reset Type
0 = No
1 = 4 to 20 mA
2 = Remote Temp
3 = Water DT
0 to 3 0
Degrees Reset At 20 mA –30.0 to 30.0 ^F 10.0
Maximum Deg Temp Reset –30.0 to 30.0 ^F 10.0
Remote Temp Full Reset –40.0 to 245.0 °F 65.0
Remote Temp No Reset –40.0 to 245.0 °F 85.0
Deg Reset Water DT Full –30.0 to 30.0 ^F 10.0
Controlled DT Full Reset 0.0 to 15.0 ^F 0.0
Controlled DT No Reset 0.0 to 15.0 ^F 10.0